| 2007-03-06 11:54:00 | *****DENIED***** |
| | |
| | |
| | 1.ON SHEET A-1 UNDER PROJECT INFORMATION NOTE 1, LIFE |
| | SAFETY SHALL COMPLY WITH NFPA 101 2003 EDITION. |
| | |
| | 2.ON SHEET A-1 UNDER APPLICABLE CODES, THE FLORIDA |
| | FIRE PREVENTION CODE 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 3.ON SHEET A-2 AND A-3, ADD " STRUCTURES UNDERGOING |
| | CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS |
| | SHALL COMPLY WITH NFPA 241". |
| | |
| | 4.ON SHEET A-6 AND A-7 NOTE 13, MAKE REFERENCE TO |
| | NFPA 241 NOT 2.4.1. |
| | |
| | 5.SPECIFY WHAT THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS (IN COMPLIANCE WITH NFPA 101 - 39.3.3.2 ) ARE |
| | TO BE.AMEND SHEET A-6 AND A-7 UNDER FINISH NOTE (A) |
| | AND SHEET A-10 NOTE UNDER ROOM FINISH SCHEDULE. |
| | |
| | 6.ON SHEET A-10A UNDER DOOR SCHEDULE, DOORS SHALL |
| | COMPLY WITH NFPA 101, 7.2.1 AND 7.2.1.5NOT 5-2.1.5 |
| | |
| | 7.DOORS WHICH LEAD DIRECTLY LEADING TO AN EXIT ACCESS |
| | CORRIDOR SHALL BE FIRE-RATED AND COMPLY WITH NFPA 80. |
| | |
| | 8.PROVIDE A LIFE SAFETY PLAN SHEET FOR THE THE SECOND |
| | FLOOR AND THE THIRD FLOOR SHOWING THE TRAVELING |
| | DISTANCE TO THE EXIT(S).THE LOCATION OF THE EXIT |
| | LIGHTS, EMERGENCY LIGHTS, AND FIRE EXTINGUISHERS |
| | (SATISFYING THE 75' TRAVEL DISTANCE REQUIREMENT) MAY BE |
| | INCLUDED. |
| | |
| | 9.SEPARATE PLANS AND PERMITS WILL BE REQUIRED FOR THE |
| | FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM |
| | MODIFICATIONS/REMODEL. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| | WAS ADDRESSED. |
| | |
| | |