Plan Review Notes
Plan Review Notes For Permit 07011148
Permit Number 07011148
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-06 11:54:00*****DENIED*****
  
  
 1.ON SHEET A-1 UNDER PROJECT INFORMATION NOTE 1, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101 2003 EDITION.
  
 2.ON SHEET A-1 UNDER APPLICABLE CODES, THE FLORIDA
 FIRE PREVENTION CODE 2004 EDITION SHALL BE REFERENCED.
  
 3.ON SHEET A-2 AND A-3, ADD " STRUCTURES UNDERGOING
 CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241".
  
 4.ON SHEET A-6 AND A-7 NOTE 13, MAKE REFERENCE TO
 NFPA 241 NOT 2.4.1.
  
 5.SPECIFY WHAT THE INTERIOR WALL AND CEILING FINISH
 MATERIALS (IN COMPLIANCE WITH NFPA 101 - 39.3.3.2 ) ARE
 TO BE.AMEND SHEET A-6 AND A-7 UNDER FINISH NOTE (A)
 AND SHEET A-10 NOTE UNDER ROOM FINISH SCHEDULE.
  
 6.ON SHEET A-10A UNDER DOOR SCHEDULE, DOORS SHALL
 COMPLY WITH NFPA 101, 7.2.1 AND 7.2.1.5NOT 5-2.1.5
  
 7.DOORS WHICH LEAD DIRECTLY LEADING TO AN EXIT ACCESS
 CORRIDOR SHALL BE FIRE-RATED AND COMPLY WITH NFPA 80.
  
 8.PROVIDE A LIFE SAFETY PLAN SHEET FOR THE THE SECOND
 FLOOR AND THE THIRD FLOOR SHOWING THE TRAVELING
 DISTANCE TO THE EXIT(S).THE LOCATION OF THE EXIT
 LIGHTS, EMERGENCY LIGHTS, AND FIRE EXTINGUISHERS
 (SATISFYING THE 75' TRAVEL DISTANCE REQUIREMENT) MAY BE
 INCLUDED.
  
 9.SEPARATE PLANS AND PERMITS WILL BE REQUIRED FOR THE
 FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 MODIFICATIONS/REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED.
  
  