| Date |
Text |
| 2007-02-09 16:04:01 | ***** UNSAT ***** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE CODES SHALL BE STATED ON THE |
| | PLANS. ALL APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE |
| | UNDER THE 2006 REVISIONS TO THE 2004 FBC AND THE 2005 |
| | NFPA-70. |
| | PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE |
| | STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS |
| | STATE LATEST EDITION. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON |
| | PLANS. |
| | FBC 106.1.2, |
| | FAC 61G1-16.004 |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER |
| | FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004. |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 4) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH THE PANEL SCHEDULES. PLEASE |
| | COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE WITH THE |
| | PANEL SCHEDULE(S) AND LIGHTING CONTROLS. PLEASE SEE |
| | SOME CIRCUITS WHICH ARE NOT INDICATED, PLEASE SEE SOME |
| | ROOMS WHICH ARE NOT DEFINED, PLEASE SEE PANEL SCHEDULES |
| | WHICH INDICATE MANY AS GEN LTS AND GEN RECEPTS. |
| | PLEASE SEE THE FOLLOWING TEXT FROM THE CODE. *SECTION |
| | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 310.16, 240.4, 408.4, ETC |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND |
| | PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2. |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETE SCHEDULING FOR THE |
| | TIMES IN USE FOR THE LIGHTING CONTROL SYSTEM. PLEASE |
| | SEE THE SECTION OF THE CODE OF CHAPTER 13 QUOTED AS 413 |
| | SHOULD BE 415. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS |
| | MISSING CONTROLS FOR SEPARATE SPACES. |
| | PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND |
| | CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE |
| | MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S). |
| | (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS |
| | ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES |
| | FOR COMPLIANCE WITH CHAPTER 13. |
| | |
| | 7) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR STROBES |
| | AND HORNS OR COMBO DEVICES. |
| | PLEASE SEE FBC 200411-4.28.1, .2 AND .3(4). |
| | |
| | 8) NOTE: PLEASE KNOW THAT ANY SECURITY CAMERAS/ITEMS |
| | SHALL BE UNDER A SEPARATE PERMIT AND PLANS. |
| | PLEASE KNOW THAT ALL CONTROL DEVICES FOR ANY ACCESS |
| | CONTROL SYSTEMS SHALL NOT IMPEDE EGRESS IN ANYWAY UNDER |
| | NORMAL POWER CONDITIONS OR UNDER EMERGENCY POWER. |
| | NFPA-101 CHAPTER 7 |
| | |
| | 9) NOTE: PLEASE SEE ROOM ON 3RD FLOOR SEEMS TO BE AN IT |
| | ROOM AND PLANS NEED TO MEET NFPA-75 AND NEC/NFPA-70 645 |
| | FOR REQUIRED MEANS OF DISCONNECTS ETC. |
| | PLEASE SEE 645.10, 645.11 ETC. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | UPS SYSTEMS BEING INSTALLED. |
| | PLEASE BE SURE THESE SHEETS CONTAIN THE LISTING |
| | INFORMATION FROM A NRTL. |
| | 110.3, |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 10) NOTE: PLEASE SHOW ALL PANELS AND SERVICE EQUIPMENT |
| | ON PLANS. |
| | PLEASE SHOW THE LOCATIONS OF TRANSFORMERS , DISCONNECTS |
| | AND PANELS. |
| | 110.26, 240.24, 408.7, 450 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT |
| | PROTECTION FOR THE TRANSFORMER(S). |
| | PLEASE SEE MAXIMUM OCP OF 125% UNLESS MEETING EXCEPTION |
| | AND NOTE #3. |
| | |
| | 12) NOTE: PLEASE COMPLETE RISER SHOWING ALL FEEDS FROM |
| | BUS-DUCT ETC. |
| | PLEASE SEE THAT AT THIS TIME THERE ARE SEVERAL ITEMS |
| | WHICH CAN NOT BE VERIFIED. |
| | PLEASE SEE #LC, PLEASE SEE TRANSFORMER LABELING, PLEASE |
| | SEE MISSING FEEDERS ON RISER, PLEASE SEE PLANS APPEAR |
| | TO SHOW MULTIPLE TAPS FROM ONE TRANSFORMER AND ONLY ONE |
| | OCP AT HV PANEL? |
| | PLEASE CORRELATE RISER CONDUCTORS AS NOTED WITH THE |
| | PANEL SCHEDULES. (3MA TO UPS TRANSFORMER), NOTES #10, |
| | PANEL SCHEDULE #12 WITH 20A OCP. |
| | PLEASE SEE EXISTING PANELS WHICH ON ONE SHEETS MENTIONS |
| | MCB AS REQUIRED PER CODE, YET PANEL SCHEDULE SHOWS |
| | MLO. |
| | PLEASE SEE 240.21C, 310.16, 240.4ETC |
| | ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY |
| | CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE |
| | OR ARE MISSING AT THIS TIME. |
| | |
| | 13) NOTE: PLEASE INDICATE ANY GROUNDING ATTACHMENTS AND |
| | SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66, AND |
| | 250.50 |
| | |
| | 14) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON |
| | ALL EXISTING WITH NEW LOADS BEING ADDED. PLEASE SEE |
| | 220.10,220.12, 220.14, 220.42, ETC, CONTINUOUS LOADS AT |
| | 125% PER 215.3, 230.42 ETC. |
| | |
| | ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT |
| | YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON |
| | THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |