Plan Review Notes
Plan Review Notes For Permit 07011148
Permit Number 07011148
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-09 16:04:01***** UNSAT *****
  
  
 1) NOTE: PLEASE SEE THE CODES SHALL BE STATED ON THE
 PLANS. ALL APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE
 UNDER THE 2006 REVISIONS TO THE 2004 FBC AND THE 2005
 NFPA-70.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE
 STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS
 STATE LATEST EDITION.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON
 PLANS.
 FBC 106.1.2,
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004.
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULES. PLEASE
 COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE WITH THE
 PANEL SCHEDULE(S) AND LIGHTING CONTROLS. PLEASE SEE
 SOME CIRCUITS WHICH ARE NOT INDICATED, PLEASE SEE SOME
 ROOMS WHICH ARE NOT DEFINED, PLEASE SEE PANEL SCHEDULES
 WHICH INDICATE MANY AS GEN LTS AND GEN RECEPTS.
 PLEASE SEE THE FOLLOWING TEXT FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 310.16, 240.4, 408.4, ETC
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND
 PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2.
  
 6) NOTE: PLEASE SUBMIT COMPLETE SCHEDULING FOR THE
 TIMES IN USE FOR THE LIGHTING CONTROL SYSTEM. PLEASE
 SEE THE SECTION OF THE CODE OF CHAPTER 13 QUOTED AS 413
 SHOULD BE 415.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS
 MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND
 CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE
 MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S).
 (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS
 ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES
 FOR COMPLIANCE WITH CHAPTER 13.
  
 7) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR STROBES
 AND HORNS OR COMBO DEVICES.
 PLEASE SEE FBC 200411-4.28.1, .2 AND .3(4).
  
 8) NOTE: PLEASE KNOW THAT ANY SECURITY CAMERAS/ITEMS
 SHALL BE UNDER A SEPARATE PERMIT AND PLANS.
 PLEASE KNOW THAT ALL CONTROL DEVICES FOR ANY ACCESS
 CONTROL SYSTEMS SHALL NOT IMPEDE EGRESS IN ANYWAY UNDER
 NORMAL POWER CONDITIONS OR UNDER EMERGENCY POWER.
 NFPA-101 CHAPTER 7
  
 9) NOTE: PLEASE SEE ROOM ON 3RD FLOOR SEEMS TO BE AN IT
 ROOM AND PLANS NEED TO MEET NFPA-75 AND NEC/NFPA-70 645
 FOR REQUIRED MEANS OF DISCONNECTS ETC.
 PLEASE SEE 645.10, 645.11 ETC.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 UPS SYSTEMS BEING INSTALLED.
 PLEASE BE SURE THESE SHEETS CONTAIN THE LISTING
 INFORMATION FROM A NRTL.
 110.3,
 FBC 106.1.2 ADMIN SECTION.
  
 10) NOTE: PLEASE SHOW ALL PANELS AND SERVICE EQUIPMENT
 ON PLANS.
 PLEASE SHOW THE LOCATIONS OF TRANSFORMERS , DISCONNECTS
 AND PANELS.
 110.26, 240.24, 408.7, 450 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT
 PROTECTION FOR THE TRANSFORMER(S).
 PLEASE SEE MAXIMUM OCP OF 125% UNLESS MEETING EXCEPTION
 AND NOTE #3.
  
 12) NOTE: PLEASE COMPLETE RISER SHOWING ALL FEEDS FROM
 BUS-DUCT ETC.
 PLEASE SEE THAT AT THIS TIME THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE VERIFIED.
 PLEASE SEE #LC, PLEASE SEE TRANSFORMER LABELING, PLEASE
 SEE MISSING FEEDERS ON RISER, PLEASE SEE PLANS APPEAR
 TO SHOW MULTIPLE TAPS FROM ONE TRANSFORMER AND ONLY ONE
 OCP AT HV PANEL?
 PLEASE CORRELATE RISER CONDUCTORS AS NOTED WITH THE
 PANEL SCHEDULES. (3MA TO UPS TRANSFORMER), NOTES #10,
 PANEL SCHEDULE #12 WITH 20A OCP.
 PLEASE SEE EXISTING PANELS WHICH ON ONE SHEETS MENTIONS
 MCB AS REQUIRED PER CODE, YET PANEL SCHEDULE SHOWS
 MLO.
 PLEASE SEE 240.21C, 310.16, 240.4ETC
 ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY
 CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE
 OR ARE MISSING AT THIS TIME.
  
 13) NOTE: PLEASE INDICATE ANY GROUNDING ATTACHMENTS AND
 SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66, AND
 250.50
  
 14) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON
 ALL EXISTING WITH NEW LOADS BEING ADDED. PLEASE SEE
 220.10,220.12, 220.14, 220.42, ETC, CONTINUOUS LOADS AT
 125% PER 215.3, 230.42 ETC.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT
 YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved