| Notes |
| Date |
Text |
| 2007-11-17 11:08:48 | **************PROVISO***************** | | | ACCESS PANELS FOR CLEAN-OUTS IN HORIZONTAL GREASE DUCTS | | | SHALL BE SPACED NOT MORE THAN 20 FEET APART IN | | | ACCORDANCE WITH FBC,M 506.3.9, NOT ONLY AT CHANGES OF | | | DIRECTION AS INDICATED ON PG M-3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|