| 2007-08-23 08:50:48 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S |
| | WRITTEN RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. THERE WAS NO WRITTEN RESPONSE TO THIS COMMENT |
| | PROVIDED AND NO CHANG SHOWN ON PLANS. PLEASE SHOW HOW |
| | THIS ITEM IS TO BE ADDRESSED AND RESUBMIT. |
| | |
| | 4. THERE IS NO FIRE DAMPER SHOWN ON 20 INCH ROUND DUCT |
| | PENETRATING THE RATED TEMPORARY BARRIER. SHOW OPENING |
| | PROTECTIVES PER FBC,M 607.5. |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |
| | 7. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| | FOR THIS REVIEW. PLEASE INCLUDE THIS INFORMATION ON THE |
| | PLANS. SEE FBC 106.1.1 |
| | |
| | 8. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| | FOR THIS REVIEW. HOWEVER, THE RELEVANT INFORMATION HAS |
| | BEEN ADDED TO THE PLANS. THIS COMMENT HAS BEEN |
| | ADEQUATELY ADDRESSED. |
| | |
| | 9. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| | FOR THIS REVIEW. NOTE 18 ON PG M-3 CALLS FOR DUCT TO BE |
| | SLOPED AT MIN. 1 INCH PER FOOT. IS THIS INTENTIONAL |
| | BECAUSE THE HORIZONTAL DUCT MAY BE IN EXCESS OF 75 |
| | FEET? THE 9X9 DUCT FOR HOOD #7 WOULD HAVE A RISE OF |
| | MORE THAN 4 FEET BEFORE IT REACHES THE LARGER DUCT. |
| | PLEASE VERIFY THAT THIS IS EVEN FEASIBLE WITH FIELD |
| | CONDITIONS. |
| | |
| | 10. THERE WERE NO SPECIFICATIONS SUBMITTED WITH PLANS |
| | FOR THIS REVIEW. ALSO, THERE ARE NO CLEANOUTS SHOWN ON |
| | THE 9X9 GREASE DUCT. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 11. OK |
| | |
| | 12. OK |
| | |
| | 13. PLEASE INDICATE ON PLANS HOW THE ADDED FIRE/SMOKE |
| | DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH FBC,M |
| | 607.5.4.1. |
| | |
| | 14. DRAWING S-1 ATTACHED TO FRONT OF PLANS: PROVIDE TWO |
| | SETS WITH ORIGINAL SEAL AND DATE/SIGNATURE PER FAC |
| | 61G15-23.002 |
| | |
| | NEW COMMENT: THERE HAS BEEN A CHANGE OF CONTRACTOR FORM |
| | FILED WITH A NEW PERMIT APPPLICATION FOR JP HURBON, |
| | INC. HOWEVER, ONE OF THE SUBCONTRACTORS HAS ALSO BEEN |
| | CHANGED ON THE PERMIT APPLICATION FROM BRADLEY HEATING |
| | AND AIR CONDITIONING, INC. TO FARMER & IRWIN CORP. AN |
| | ADDITIONAL CHANGE OF CONTRACTOR FORM MUST BE FILED TO |
| | FACILITATE THIS CHANGE. |
| | |