| 2007-02-04 18:55:42 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN |
| | SHALL BE STATED ON THE PLANS. |
| | PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF |
| | FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND |
| | THE 2005 NFPA-70. |
| | PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A |
| | MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER |
| | TRADES. |
| | 2004 FBC W/2006 (REVISIONS) |
| | 2005 NFPA-70 NEC. |
| | |
| | 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW |
| | CIRCUIT(S) LOADS ON NEW AND EXISTING. PLEASE SHOW THE |
| | CONDUCTOR SIZE(S), OVER CURRENT PROTECTION ETC. |
| | 408.4, 310.16, 240.4. |
| | PLEASE INDICATE ANY CONTINUOUS LOADS AT 125% 215.3, |
| | 230.42/ MOTOR LOADS? |
| | |
| | 3) NOTE: PLEASE INDICATE NEW OR EXISTING SHUNT/SHUT |
| | DOWN OF ALL ELECTRICAL UNDER HOOD PER NFPA-96. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |