| Date |
Text |
| 2007-03-06 17:12:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)DO NOT REFER TO THE "TYPICAL NOTES" TO SHOW CODE |
| | COMPLIANCE AS YOUR NOTES ARE CONFLICTING AND ARE NOT |
| | CODE COMPLIANT. |
| | |
| | 2.)NOTE 6 STATES THAT STAIRS GUARDRAILS TO BE 34" TO |
| | 38" HIGH, NOTE 4 STATES THAT GUARDRAILS ARE TO BE 42" |
| | HIGH. |
| | |
| | 3.)IN SEVERAL PLACES, THE PLAN STATES "AS PER FBC |
| | 2004 1009".DETAILS ARE TO BE SPECIFIC FBC*106.1.1. |
| | |
| | 4.)PROVIDE A PERMIT NUMBER FOR WHAT YOU CALL |
| | ?EXISTING STAIRS? ON THE PLAN.THE DIMENSIONS ARE TO |
| | COMPLY WITH FBC1009.ON THE PLAN, EVERY RISER IS SHOWN |
| | AT A DIFFERENT DIMENSION RANGING FROM 2? TO 6? ON ONE |
| | SIDE, 5? AND 7? ON THE OTHER SIDE, AND THE TREADS ARE |
| | SHOWN AT 2?11? AND 3?2?.SEE FBC1009.3.IT APPEARS |
| | THAT THE ?EXISTING STAIRS? WERE NOT BUILT IN COMPLIANCE |
| | WITH THE CURRENT BUILDING CODE AND PRESENT A HAZARD. |
| | |
| | 5.)DECLARE GOVERNING CODE, INCLUDING 2006 AMENDMENTS, |
| | AND EXISTING BUILDING CODE. |
| | |
| | 6.)IS THIS A CHANGE OF OCCUPANCY?OUR RECORDS SHOW |
| | AN AUTO BODY SHOP IN THIS LOCATION. |
| | |
| | 7.)THE GUARD IS TO COMPLY WITH FBC1012 AND FBC1607.7. |
| | SHOW COMPLIANCE ON THE PLAN. |
| | |
| | 8.)MANY PLACES ON THE PLAN STATE "BY OTHERS".WHAT |
| | DOES THIS MEAN?PLANS ARE TO SHOW CODE COMPLIANCE AND |
| | SCOPE OF WORK.APPLICATION STATES "ADD GUARD RAIL TO |
| | EXISTING CONCRETE WALKWAY AND LEVEL IT."HOW CAN YOU |
| | EXCLUDE THE GUARDRAIL IF THAT'S THE PURPOSE OF THE |
| | APPLICATION?WHERE IS THE CONCRETE WALKWAY?WHAT DOES |
| | "LEVEL IT" MEAN?PLANS SHOULD CLEARLY SHOW SCOPE OF |
| | WORK AND BE CONSISTENT WITH THE APPLICATION. |
| | |
| | 9.)THE CONTRACTOR DECLARED A $350 VALUE.PROVIDE A |
| | REASONABLE VALUE OR A VALUATION ADJUSTMENT WILL BE DONE |
| | FOR YOU USING MARSHALL & SWIFT. |
| | |
| | 10.)HANDRAILS REQUIRED ON BOTH SIDES OF THE STAIR, |
| | FBC1009.11.SHOW ALL DETAILS TO SHOW COMPLIANCE WITH |
| | FBC11-4.9.4 AND FBC1009. |
| | |
| | 11.)THE PLANS STATE ?PRE-FABRIC. GUARDRAIL PER 1108.5 |
| | FBC SEE TYPICAL NOTES BY OTHERS.?WHAT IS BY OTHERS, |
| | THE TYPICAL NOTES OR THE GUARDRAIL?SEE COMMENT 8 |
| | ABOVE REGARDING WHAT INFORMATION IS REQUIRED TO BE ON |
| | THE PLAN.SECTION 1108.5 DOES NOT EXIST IN THE FLORIDA |
| | BUILDING CODE, NOT SURE OF THE PURPOSE OF THIS NOTE. |
| | |
| | 12.)DIAZ DRAFTING SERVICES HAS ALREADY BEEN INFORMED |
| | BY THIS DEPARTMENT THAT THEY ARE NOT LICENSED TO DO |
| | DESIGN WORK FOR COMMERCIAL PROPERTIES.CONTINUED |
| | NONCOMPLIANCE WILL RESULT IN A COMPLAINT AGAINST THE |
| | COMPANY.DUE TO THIS ISSUE AND THE DEFICIENCIES IN THE |
| | PLAN, A SET HAS BEEN RETAINED. |
| | |
| | 13.)THE NOTES STATE THAT THE BOTTOM RAIL SHALL REJECT |
| | THE PASSAGE OF A 2" OBJECT.HOWEVER, A 3" AND 5" GAP |
| | IS SHOWN BETWEEN THE BOTTOM OF THE BALUSTERS AND THE |
| | "PLATFORM".DETAILS ARE TO BE CONSISTENT AND CODE |
| | COMPLIANT.SEE FBC1012. |
| | |