Plan Review Notes
Plan Review Notes For Permit 07011114
Permit Number 07011114
Review Stop G
Sequence Number 2
Notes
Date Text
2007-07-02 11:14:38DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** VALUE OF GENERATOR IS TO LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: PLEASE CORRECT THIS PRIOR TO THE RESUBMITTAL.
  
 2. **NO/OK** PLEASE PROVIDE MANUFACTURER
 SPECIFICATIONS INDICATING RECOMMENDING SETBACKS OF
 GENERATOR TO STRUCTURES AND TO VERIFY BTU LOAD.
 NOTE: THE MANUFACTURER SPECIFICATIONS REQUESTED FOR THE
 RESUBMITTAL INDICATING THE RECOMMENDED SETBACKS OF
 GENERATOR TO STRUCTURES WAS NOT PROVIDED. PLEASE
 PROVIDE THIS INFORMATION ON THE NEXT RESUBMITTAL.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 ** THE FOLLOWING IS A NEW COMMENT **
  
 6. SHEET C-1: THE LONGEST RUN OF 31' ON THE RESUBMITTED
 GAS ISOMETRIC IS WRONG. THE CORRECT LONGEST RUN ON THE
 GAS SYSTEM IS 44' FROM THE NEWLY PROVIDED INFORMATION.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 ******IMORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721