2007-06-22 15:20:23 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S
 FOR THE GENERATOR. THE SETBACK IS NOT STATED IN THE
 PLANS PROVIDED.
  
 NOTE: THE ATS IS THE FIRST MEANS OF DISCONNECT FROM THE
 SERVICE AS IT IS PLACED BETWEEN THE METER AND PANEL.
 THE NEUTRAL MUST BE ISOLATED FROM THE GROUNDS IN THE
 EXISTING PANEL PANEL. 250.24(C).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718