Plan Review Notes
Plan Review Notes For Permit 07011114
Permit Number 07011114
Review Stop G
Sequence Number 1
Notes
Date Text
2007-02-14 10:22:10DENIED
 REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE OF GENERATOR IS TO LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 2. PLEASE PROVIDE MANUFACTURER SPECIFICATIONS
 INDICATING RECOMMENDING SETBACKS OF GENERATOR TO
 STRUCTURES AND TO VERIFY BTU LOAD.
  
 3. SHEET C-1 INDICATES THE EXISTING GAS PIPE TO THE
 EXISTING WATER HEATER BEING 3/8". THIS IS WRONG PER
 FBC-2004 TABLE 402.4(8) AND FBC-2004 FUEL GAS , SECTION
 402.4.1 LONGEST LENGTH METHOD, THE GAS PIPE TO THE
 EXISTING WATER HEATER NEEDS TO BE INCREASED TO 1/2".
 PLEASE REFERENCE THE ATTACHED TABLE INDICATING THIS.
 PLEASE CORRECT AND RESBMIT.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON
 THE GAS ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND
 RESUBMIT.
  
 5. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL MATERIAL TYPES ARE INDICATED ON THE GAS
 ISOMETRIC ON SHEET C-1. PLEASE CORRECT AND RESUBMIT.
  
 ******IMORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  