| 2007-02-12 10:18:43 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | 2} PROVIDE MANUFACTURERS SPECIFICATIONS |
| | INDICATING RECOMMENDED SETBACKS AND |
| | ELECTRICAL SPEC'S FOR THE GENERATOR AND |
| | TRANSFER SWITCH. |
| | |
| | IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS BEING |
| | TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED PER |
| | ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT ANY |
| | TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL |
| | CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO |
| | "SELECT" WHICH CIRCUITS WILL BE DE-ENERGIZED. |
| | |
| | ALSO THE NOTE IN THE "LOAD CALCULATION" AREA REGARDING |
| | HURRICANE SEASON IS NOT APPLICABLE AS POWER FROM THE |
| | UTILITY CAN BE INTERUPTED AT ANY TIME REGARDLESS OF |
| | SEASON.THE HEAT LOAD MUST BE CALCULATED PER ARTICLE 220 |
| | IF THAT LOAD IS CONNECTED TO THE PANEL BEING ENERGIZED |
| | BY THE TRANSFER SWITCH. |
| | |
| | 3}PROVIDE A CALCULATION OF ALL LOADS TO BE SUPPLIED |
| | BY THE GENERATOR: AN OPTIONAL STANDBY SYSTEM SHALL HAVE |
| | ADEQUATE CAPACITY AND RATING FOR THE SUPPLY OF ALL |
| | EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME, 702.5 |
| | 2005 NEC. IN THE EVENT A MANUAL TRANSFER SWICH IS |
| | INSTALLED, THESE CALCULATIONS WOULD NOT BE REQUIRED AS |
| | SOMEONE WOULD HAVE TO BE PRESENT TO SELECT THE TRANSFER |
| | AND THEREFORE THE LOADS. |
| | |
| | 4} NOTE #2, SHEET E-1, INCORRECTLY REFERENCES ARTICLE |
| | 110.16, WHICH IS FROM THE 1996 CODE, FLORIDA HAS |
| | CURRENTLY ADOPTED THE 2005 NEC AS OF 12/8/2006. |
| | |
| | 5} THE SITE DIAGRAM ON SHEET C-1 INDICATES THE ATS |
| | BEING FED DIRECTLY FROM THE METER AND GENERATOR. THE |
| | RISER ON SHEET E-1 INDICATES THE METER FEED TO THE |
| | PANEL. THE ATS MUST BE SERVICE RATED PER 225.36, 230.66 |
| | AND RATED PER 110.9 AND 110.10FOR AIC FROM THE |
| | UTILITY IF IN BEING INSTALLED AS SERVICE EQUIPMENT. |
| | PLEASE CLARIFY THE INSTALLATION PROPOSED AND CORRELATE |
| | DRAWINGS. OPTIONAL STANDBY SYSTEM EQUIPMENT SHALL BE |
| | SUITABLE FOR THE MAXIMUM AVAILABLE FAULT CURRENT AT ITS |
| | TERMINALS.702.5. |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |