Date Text
2007-02-12 10:18:43 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS BEING
 TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED PER
 ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT ANY
 TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL
 CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO
 "SELECT" WHICH CIRCUITS WILL BE DE-ENERGIZED.
  
 ALSO THE NOTE IN THE "LOAD CALCULATION" AREA REGARDING
 HURRICANE SEASON IS NOT APPLICABLE AS POWER FROM THE
 UTILITY CAN BE INTERUPTED AT ANY TIME REGARDLESS OF
 SEASON.THE HEAT LOAD MUST BE CALCULATED PER ARTICLE 220
 IF THAT LOAD IS CONNECTED TO THE PANEL BEING ENERGIZED
 BY THE TRANSFER SWITCH.
  
 3}PROVIDE A CALCULATION OF ALL LOADS TO BE SUPPLIED
 BY THE GENERATOR: AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE SUPPLY OF ALL
 EQUIPMENT INTENDED TO BE OPERATED AT ONE TIME, 702.5
 2005 NEC. IN THE EVENT A MANUAL TRANSFER SWICH IS
 INSTALLED, THESE CALCULATIONS WOULD NOT BE REQUIRED AS
 SOMEONE WOULD HAVE TO BE PRESENT TO SELECT THE TRANSFER
 AND THEREFORE THE LOADS.
  
 4} NOTE #2, SHEET E-1, INCORRECTLY REFERENCES ARTICLE
 110.16, WHICH IS FROM THE 1996 CODE, FLORIDA HAS
 CURRENTLY ADOPTED THE 2005 NEC AS OF 12/8/2006.
  
 5} THE SITE DIAGRAM ON SHEET C-1 INDICATES THE ATS
 BEING FED DIRECTLY FROM THE METER AND GENERATOR. THE
 RISER ON SHEET E-1 INDICATES THE METER FEED TO THE
 PANEL. THE ATS MUST BE SERVICE RATED PER 225.36, 230.66
 AND RATED PER 110.9 AND 110.10FOR AIC FROM THE
 UTILITY IF IN BEING INSTALLED AS SERVICE EQUIPMENT.
 PLEASE CLARIFY THE INSTALLATION PROPOSED AND CORRELATE
 DRAWINGS. OPTIONAL STANDBY SYSTEM EQUIPMENT SHALL BE
 SUITABLE FOR THE MAXIMUM AVAILABLE FAULT CURRENT AT ITS
 TERMINALS.702.5.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.