Plan Review Notes
Plan Review Notes For Permit 07011105
Permit Number 07011105
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-20 18:56:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
  
 1. SHT 6 0F 6 INDICATES THE SUPPORTS FOR THE PIPING IS
 7'0" ON CENTER. THE MAXIMUM HANGER/SUPPORT SPACING FOR
 PVC PIPE IS 4'0" PER TABLE 308.5.
 ****RESPONSE NOTED, BUT PER SECTION 102.1 WHERE, IN ANY
 SPECIFIC CASE, DIFFERENT SECTIONS OF THIS CODE SPECIFY
 DIFFERENT MATERIALS, METHODS OF CONSTRUCTION OR OTHER
 REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. THIS
 INCLUDES MANUF. SPECIFICATION.
  
 2. OK
 3. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731