Plan Review Notes
Plan Review Notes For Permit 07011105
Permit Number 07011105
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-09 18:17:48BUILDING PLAN REVIEW
 PERMIT: 07011105
 ADD: TO BE DETERMINED
 CONT:PLAN REVIEW
 ISSAC KOVNER
 TEL: (561)494-1091
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE CONTACT LILI URSA @ ADDRESSING FOR CORRECT
 ADDRESS AND ASSOCIATED PCN.
  
 3)) PLEASE PROVIDE (2) SIGNED SEALED ORIGINAL SIGNATURE
 SOILS REPORTDATED JULY 5, 2000
 BY CURTIS, ROOS, PE NODARSE AND ASSOC. FBC 1802.2.1
 QUESTIONABLE SOILS,
 NOTES FROM 6"X6" TIMBER PILE INDICATE TO JET TO BEARING
 CAPACITY OF 2500 PSF, THE ACENTRIC LOADING
 APPEARS TO LOAD THE PILE NEAREST THE PIPE OVER3000
 LBS WITH THE LOAD OF THE WATER AND PVC PIPE, WILL THE
 ONE PILE REQUIRE ?
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4)109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) FLOOD ZONE
 H ) FLOOD ELEVATION
  
 6) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7)SHEET S-5 UNDER THE GENERAL TIMBER NOTES THE PLANS
  
 INDICATE THE USE OF ACQ PRESSURE TREATED TIMBERS
 BUT DO NOT SPECIFY THE MINIMUM RETENTION(KILOGRAMS
 PER CUBIC METER)
 TO BE USED FOR BELOW THE SOIL AND FRESH WATER USE?
 2304.11.4.
  
 8) SHEET S-6INDICATES THE USE OF VARIOUS TIE DOWN
 STRAPS AND BOLTS, BUT THERE IS NO MENTION AS TO THE
 FINISH COATING OF THESE FASTENERS.SINCE THEY WILL BE
 USED IN CONJUNCTION WITH ACQ TREATED LUMBER PLEASE
 PROVIDE THE TYPE OF COATING TO BE APPLIED TO THE
 FASTENERS.
 2304.9.5 FASTENERS IN PRESERVATIVE-TREATED AND
 FIRE-RETARDANT-TREATED WOOD.
 FASTENERS FOR PRESERVATIVE-TREATED AND
 FIRE-RETARDANT-TREATED WOOD SHALL BE OF HOT-DIPPED
 ZINC-COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON
 BRONZE OR COPPER. FASTENINGS FOR WOOD FOUNDATIONS SHALL
 BE AS REQUIRED IN AF&PA TECHNICAL REPORT NO. 7.
  
 2304.9.6 LOAD PATH.
 WHERE WALL FRAMING MEMBERS ARE NOT CONTINUOUS FROM
 FOUNDATION SILL TO ROOF, THE MEMBERS SHALL BE SECURED
 TO ENSURE A CONTINUOUS LOAD PATH. WHERE REQUIRED, SHEET
 METAL CLAMPS, TIES OR CLIPS SHALL BE FORMED OF
 GALVANIZED STEEL OR OTHER APPROVED CORROSION -RESISTANT
 MATERIAL NOT LESS THAN 0.040 INCH (1.01 MM) NOMINAL
 THICKNESS.
  
 9) ENGINEER OF RECORD:
 IN ADDITION TO SIGNING, SEALING AND
 DATING EACH PAGE OF THE PLANS, THE
 ENGINEER IN RESPONSIBLE CHARGE MUST
 LEGIBLY INDICATE IN A TITLE BLOCK THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 PLAN SHEET. 61G15-23.002 F.A.C.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved