| 2007-03-09 16:46:12 | BUILDING PLAN REVIEW |
| | PERMIT: 07011099 |
| | ADD: 14228TH STREET |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3)WPB AMENDMENTS 108.3*IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALLBE |
| | THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | ARCHITECTURAL AND DESIGN FEES, EXCLUDING LAND. OUR |
| | VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND |
| | MEANS COST ANALYSIS SERVICES. |
| | |
| | 4)THE REFERENCE TO SEC. 905.22 F.B.C. ON SHEET 2 OF |
| | 5HAS NOTHING TO DO WITH SMOKE DECTORS. SEE2004 |
| | RESIDENTIAL F.B.C. SEC.313 FOR MORE INFORMATION. AND |
| | EITHER REMOVE THAT REFERENCE OR SHOW WHERE IT APPLIES |
| | TO THIS PROJECT. |
| | |
| | 5)R807.1 ATTIC ACCESS . |
| | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER |
| | THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| | HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| | POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| | FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. |
| | |
| | 6)ON THE ELEVATION DETAILS SHOW THE DIMENTIONS OF THE |
| | WINDOWS INCLUDING THE HEIGHT OF THE WIDOWSILL AND THE |
| | DISTANCE BETWEEN EACH WINDOW AND FROM THE CORNERS. |
| | |
| | 7)THE MINIMUM UNIFORM DISTRIBUTED LIVE LOAD FOR |
| | ATTICS WITHOUT STORAGE IS 10PSF. THE REPORT FROM THE |
| | TRUSS DESIGN ENGINEER INDICATE A 0.0 BCLL. CLARIFY. |
| | |
| | 8)61G15-23.002 (2)ALL INFORMATION BEING FILED FOR |
| | PUBLIC RECORD SHALL BE ORIGINALLY SIGN AND SEALED.THE |
| | SIGNATURE ON THE TRUSS REPORTS IS A PHOTO COPY.EACH |
| | SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED UNDER |
| | THE PROVISIONS OF CH.471, F.S., SHALL BE SEALED, SIGNED |
| | AND DATED BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE |
| | CHARGE. ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME,ADDRESS,AND LICENSE NUMBER ON EACH SHEET. |
| | |
| | 9) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.THE PRODUCT APPROVALS SHALL |
| | BE APPROVED IN WRITING BY THE DESIGNER OF RRECORD. |
| | |
| | 10) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |