| Date |
Text |
| 2007-03-01 10:51:35 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE OWNER/AGENT IS REQUIRED TO SIGNE THE ENERGY |
| | CALC. FORM PER FBC CHAPTER 13. |
| | |
| | 3) THE NUMBER OF BEDROOMS ON THE PLANS IS 2 AND THE |
| | ENERGY CALC. FORM LISTS 1. PLEASE CORRECT. |
| | |
| | 4) THE CONDITIONED FLOOR AREA FOR THE STRUCTURE IS |
| | LISTED AS 1058 SQFT ON THE ENERGY CALC. FORM AND BASED |
| | ON THE PLANS THE STRUCTURE IS 1243 SQFT. PLEASE |
| | CORRECT. |
| | |
| | 5) SPECIFY THE THICKNESS OF THE DRYWALL FOR THE WALLS |
| | AND CEILING ON THE WALL SECTION ON SHEET 2. |
| | |
| | 6) SPECIFY THE NUMBER, SIZES AND TYPES OF FASTENERS |
| | THAT WILL BE USED WITH THE CONNECTORS SHOWN IN THE WALL |
| | SECTION ON SHEET 2. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE USP AND SIMPSON |
| | CONNECTORS SPECIFIED ON THE PLANS. |
| | |
| | 8)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 9)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |