| 2007-02-21 08:43:51 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE SEPARATE GAS PERMIT: |
| | |
| | 1. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | THE BTU INFORMATION SUBMITTED IS CONFLICTING FROM ONE |
| | PAGE TO THE OTHER. THE NEXT TO LAST SHEET INDICATES THE |
| | BTU LOAD TO BE 905,000 BTU'S, BUT THE FINAL PAGE |
| | INDICATES FUEL CONSUMPTION TO BE 4200 CFH, (4,536,000 |
| | BTU'S). PLEASE CLARIFY AS THIS IS A LARGE DISCREPENCY. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 4. THE PERSON RESPONSIBLE FOR THE DESIGN OF THE PIPING |
| | SHALL PRINT THEIR NAME AND SIGN THE PLANS. SECTION |
| | 106.1. |
| | |
| | 5. PER TABLE 402.4.3 THE PIPING FOR 905,000 BTU AT 150 |
| | FEET SHALL BE A MINIMUM 1" PIPE. IF THE MAXIMUM BTU |
| | LOAD IS 4,536,000 BTU AS INDICATED ON THE LAST PAGE OF |
| | THE SUBMITTAL, THEN THE PIPE SIZE SHALL BE 1-1/2". |
| | |
| | 6. PLEASE INDICATE THE MODEL NUMBER OF THE REGULATOR TO |
| | BE USED. KEEP IN MIND THE MANUF. RECOMMENDATION THAT |
| | THE REGULATOR IS WITHIN ONE SIZE OF THE MANIFOLD PIPE |
| | SIZE. SECTION 106.1.1. |
| | |