| Plan Review Notes For Permit 07011083 |
| Permit Number |
07011083 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-31 14:39:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)TWO SETS REQUIRED.ONE SET IS A PHOTOCOPY. | | | ENGINEERING IS TO BE ORIGINAL, FS471. | | | | | | 2.)SHEET 4 STILL SHOWS SCUPPERS ON THE STRUCTURAL | | | DETAIL.PLEASE CHECK ALL SHEETS AND AS THE ENGINEER | | | HAS DETERMINED THAT SCUPPERS ARE NOT REQUIRED, REMOVE | | | REFERENCES FROM THE PLAN. | | | | | | 3.)APPLICATION DESCRIPTION IS NOT CONSISTENT WITH THE | | | PLAN.APPLICATION STATES THAT INSULATION WILL BE | | | INSTALLED.WHERE?WHAT TYPE?PROVIDE A DETAIL/PLAN. | | | | | | |
|