2007-02-09 16:37:44DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MUST PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF
 WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTIONS 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2.
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4.
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3 ) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004
 PLUMBING, SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 END OF COMMENTS:
  