| 2007-02-20 18:05:16 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)A DETAIL WITH CONNECTION TYPE C3 AND C4 WAS |
| | CIRCLED.FOR SPAN OF 15FT, 47.2 PSF, ANCHOR SPACING OF |
| | 10INCHES IS NOT COMPLIANT.TO USE "GENERIC" ANCHORING, |
| | IT MUST BE COMPLIANT FOR WORST CASE.PLEASE ADDRESS. |
| | CHECK ALL OPENINGS. |
| | |
| | I HAD A TELEPHONE CONVERSATION WITH CONTRACTOR |
| | REGARDING THIS CORRECTION.CONTRACTOR INFORMED ME THAT |
| | THERE ARE NO OPENINGS OF 15 FEET.THE LARGEST SPAN FOR |
| | THIS JOB IS 121", 10 FEET.SEE SHEET 7 OF THE PRODUCT |
| | APPROVAL.A 10' SPAN WOULD BE REQUIRED TO USE THE 15' |
| | CHART (AS THE NEXT CHART SIZE DOWN IS 9', TOO SMALL FOR |
| | THE 10' SPAN).FOR A DESIGN PRESSURE OF -47.2, ANCHOR |
| | SPACING RANGES FROM 4INCHES TO 14 INCHES, AND THE |
| | 10INCH ANCHOR SPACING WHICH YOU SPECIFY IS NOT |
| | COMPLIANT FOR ALL CONNECTION TYPES. |
| | |
| | THE OTHER OPENINGS ARE LESS THAN 9 FEET.FOR -47.2, |
| | ANCHOR SPACING RANGES FROM 7 INCHES TO 18 INCHRES.THE |
| | 10INCH SPACING IS STILL NOT COMPLIANT FOR ALL |
| | CONNECTION TYPES. |
| | |
| | ONE NUMBER ON THE ANCHOR SPACING CHART WAS CIRCLED, ALL |
| | POINTS SOLID SET, FOR 6' SPAN 2INCH EDGE DISTANCE. |
| | ALSO 1/4 ITW TAPCON WAS CIRCLED.IF YOU ARE USING |
| | MULTIPLE FASTENER TYPES, PLEASE PROVIDE INFORMATION |
| | SPECIFIC TO EACH OPENING OR SPECIFY ANCHOR SPACING TO |
| | BE "WORST CASE". |
| | |
| | TO DECLARE 10" ANCHOR SPACING, YOU MUST SPECIFY WHICH |
| | CONNECTION TYPE YOU ARE USING AS NOT ALL OF THEM ARE |
| | COMPLIANT.GENERIC ANCHORING (SPECIFYING ONE ANCHOR |
| | SPACING FOR THE ENTIRE JOB) MUST BE DESIGNED TO THE |
| | WORST CASE AND MUST PROVIDE ALL INFORMATION REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | |