| Plan Review Notes For Permit 07011070 |
| Permit Number |
07011070 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-12 07:57:00 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} THERE MUST BE A DISCONNECTING MEANS FOR THE PANELS | | | SHOWN PER 230.70(A)(1) AND 225.32, THE PANEL IS LISTED | | | AS MAIN LUG ONLY. INDICATE IF THE PANEL IS AT THE | | | SERVICE AND IF SO SHOW COMPLIANCE WITH THE ABOVE | | | ARTICLES. | | | | | | 2} IF THE FIRST FLOOR IS INCLUDED IN THE ELECTRICAL | | | WORK UNDER THIS PERMIT, PROVIDE A PANEL SCHEDULE PER | | | 408.4 NEC 2005, ALSO CALCULATE THE ENTIRE SERVICE PER | | | 220. | | | | | | 3} THERE ARE NONE OF THE REQUIREDGFI CIRCUITS (210.8) | | | SHOWN ON THE FIRST FLOOR. PLEASE SHOW ONLY THE WORK TO | | | BE DONE UNDER THIS PERMIT. | | | | | | THERE IS NO ELECTRICAL WORK INDICATED ON THE | | | APPLICATION. CORRECT APPLICATION TO INCLUDE ALL WORK TO | | | BE PERMITTED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|