| Plan Review Notes For Permit 07011043 |
| Permit Number |
07011043 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-25 16:08:03 | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, PLEASE | | | CORRECT. | | | | | | 2)PAGES A-05 AND A-08 SHOW THE SPACE ABOVE THE | | | ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD | | | NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO | | | PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE | | | M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS | | | ARE UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED | | | BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|