| | DENIED/INCOMPLETE INFORMATION. |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED |
| | FROM THE PREVIOUS REVIEW: |
| | |
| | "2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR |
| | SPACE CONTROLS FOR LIGHTING".STANDARD SWITCHES ARE |
| | SHOWN ON THE PLAN.NOTE #1 ADDRESSING THIS ISSUE |
| | STATES THAT THE "SPACES LESS THAN 5000 SF". PLEASE SEE |
| | 13-101.1.4. A "SPACE" IS NOT A "BUILDING", THE |
| | "BUILDING" IS MORE THAN 5000 SF, THE "SPACE" MUST |
| | COMPLY. SHOW COMPLIANCE ON THE DRAWING, NOT IN THE |
| | NOTES.106.1.1 FBC. |
| | |
| | 3} PLEASE INDICATE CONDUCTOR SIZE ON THE PANEL SCHEDULE |
| | SO THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED. THE |
| | BRANCH CIRCUIT CONDUCTOR SIZES,AS WELL AS THE FEEDER, |
| | NEED TO BE ON THE SCHEDULE. 106.3.5.1.2(1), FBC AS |
| | AMENDED. |
| | |
| | THESE COMMENTS ARE FROM THIS REVIEW. |
| | |
| | 4} SHEET #5 OF THE CALCULATIIONS INCORRECTLY INDICATES |
| | "PASSES", THERE ARE NO LIGHTING CONTROLS SHOWN ON THE |
| | DRAWING. |
| | |
| | 5} SHEET #2 OF THE INPUT DATA REPORT INCORRECTLY |
| | INDICATES 1 FLUORESCENT FIXTURE@ 1300 WATTS FOR THE |
| | LIGHTING FOR THE SPACE. PLEASE CORRECT INDICATING ALL |
| | FIXTURES BEING USED. |
| | |
| | 6} PROVIDE A FIXTURE SCHEDULE THAT MATCHES WHAT THE |
| | ENERGY CALCULATIONS INDICATES. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW |
| | ONES, SUBMIT OLD SHEETS TO EXPEDITE |
| | REVIEW AND SUBMIT WRITTEN RESPONSE TO |
| | THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | |