| 2007-03-19 14:38:44 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM |
| | BEACH GAS PERMIT/REVISION REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR |
| | THE GAS REVISION TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE SUBMITTED ISOMETRIC REVISION DOES NOT INDICATE |
| | ALL CORRESPONDING LENGTHS PER FBC-2004 FUEL GAS. |
| | |
| | A} CORRESPONDING LENGTH TO UNDERGROUND PE PIPE FOR |
| | POOL HEATER MISSING. |
| | |
| | B} CORRESPONDING LENGTH TO NEW PIPING FOR FIREPLACE |
| | MISSING. |
| | |
| | C} CORRESPONDING LENGTH TO COOKTOP MISSING. |
| | |
| | 2. ON THE SUBMITTED REVISION THE GAS TYPE IS MISSING. |
| | ON THE PERMITTED PLAN THE GAS TYPE WAS INDICATED AS |
| | NATURAL GAS. PLEASE CLARIFY AND ON THE REVISION |
| | RESUBMITTAL. |
| | |
| | 3. ON THE SUBMITTED REVISION THE MP REGULATOR |
| | INFORMATION IS MISSING. ON THE PERMITTED PLAN THE |
| | REGULATOR FOR THE POOL HEATER IS A MAXITROL 325-7 AND |
| | THE MP REGULATOR FOR THE HOUSE IS A MAXITROL 325-5A. |
| | PLEASE CLARIFY ON THE REVISION RESUBMITTAL. |
| | |
| | 4. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE |
| | THESE VALVES ON THE REVISION RESUBMITTAL. |
| | |
| | 5. PER FBC-2004 FUEL GAS TABLE 402.4(2) THE 1" BLK. |
| | STEEL PIPE FROM THE MP REGULATOR TO THE HOUSE NEEDS TO |
| | BE INCREASED IN SIZE TO 1-1/4" DUE TO THE INCREASED BTU |
| | LOAD OF THE ADDED FIREPLACE. PLEASE CORRECT AND |
| | RESUBMIT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | NOTE: PLEASE REFERENCE THE ATTACHED PERMITTED COPY OF |
| | THE APPROVED PLANS AND THE FBC-2004 FUEL GAS TABLE |
| | 402.4(2) FOR THE REVISION RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |