| 2007-03-21 17:23:35 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) DETAIL 1/A4 SITES THE WRONG CODE SECTION FOR THE |
| | FIREBLOCKING FOR THE CONCEALED SPACES OF THE STAIRS. |
| | THE CORRECT SECTION IS FBC R602.1.2. |
| | |
| | 4) THE FIREBLOCKING MATERIAL IS REQUIRED TO COMPLY WITH |
| | FBC R602.1.2.1. THE 5/8" PLYWOOD SPECIFIED IN THE NOTES |
| | FOR DETAIL 1/A4 DOES NOT COMPLY. |
| | |
| | 5) R311.5.8.3 REQUIRES CIRCULAR STAIRS TO HAVE A |
| | MINIMUM TREAD WIDTH OF 9 INCHES WITH 1 INCH OF NOSING. |
| | DETAIL 1/A4 DOES NOT COMPLY. |
| | |
| | 6) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| | 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 7) SHOW COMPLIANCE WITH R806.2 MINIMUM AREA. |
| | THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| | THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| | EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| | TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| | THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| | REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA |
| | MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING |
| | A TRANSMISSION RATE NOT EXCEEDING 1 PERM (57.4 MG/S ? M |
| | 2 ? PA) IS INSTALLED ON THE WARM SIDE OF THE CEILING. |
| | |
| | 8)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH |
| | SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| | RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL |
| | BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT |
| | 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS |
| | SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 |
| | MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH |
| | FIGURE R803.2.3.1. |
| | |
| | 9) ON A5 THE ROOF TILE FASTENING NOTE SPECIFIES (2) #9 |
| | SCREWS. DID YOU INTEND TO SPECIFY #8 SCREWS AS LISTED |
| | IN THE ROOF TILE PRODUCT APPROVAL?I DO NOT BELIEVE #9 |
| | SCREWS ARE AVAILABLE. |
| | |
| | 10)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11)SPECIFY THE FASTENING OPTION THAT WILL BE USED TO |
| | INSTALL THE CONCRETE ROOF TILES. CIRCLE THE APPROPRIATE |
| | ITEM ON THE NOA. |
| | |
| | 12) THE NOA SUBMITTED FOR THE HANSEN ROOF TILE HAS BEEN |
| | CLOSED BY MIAMI-DADE PRODUCT CONTROL. THE CURRENT NOA |
| | FOR THE HANSEN TILE IS 02-0916.09. |
| | |
| | 13) SUBMIT PRODUCT APPROVALS FOR STRUCTURAL WINDOW |
| | MULLIONS. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR IMPACT RATED FRENCH |
| | DOORS WITHOUT SIDELITES. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE BITHUTHENE WATER |
| | PROOF MEMBRANE THAT WILL BE INSTALLED ON THE DECKS. |
| | |
| | 16) SUBMIT PRODUCT APPROVALS FOR THE FRONT ENTRY DOOR. |
| | |
| | 17) THE PLANS SPECIFY A HOLLOW METAL RAISED PANEL DOOR |
| | FOR DOOR #106. PRODUCT APPROVALS WERE SUBMITTED FOR A |
| | RAISED PANEL FIBERGLASS DOOR, BUT NOT A METAL DOOR. |
| | PLEASE CO-ORDINATE THE PLANS WITH THE PRODUCT |
| | APPROVALS. |
| | |
| | 18)THE PRODUCT APPROVAL FOR THE PGT WINDOWS HAS BEEN |
| | REVISED. THE FL NUMBER IS FL 239-R7 AND THE NEW NOA IS |
| | #05-1018.01. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |