2007-04-17 07:29:16 
  
 PROVISO
  
 THE ICE MAKER AND REFRIGERATORSHOWN ON CIRCUIT #19
 MUST NOT EXCEED 50% OF THE CIRCUIT RATING, 7.5 AMPS OR
 900 WATTS, PER 210.23(A). CHECK APPLIANCE RATINGS, ADD
 A CIRCUIT OR INCREASE CIRCUIT #19 TO A 20 AMP IF
 NECESSARY. HAVE THE RATINGS OF BOTH APPLIANCES
 AVAILABLE FOR THE INSPECTOR ON THE ROUGH ELECTRICAL
 INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718