Plan Review Notes
Plan Review Notes For Permit 07010963
Permit Number 07010963
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-26 16:05:31BUILDING PLAN REVIEW
 PERMIT: 07010963
 ADD: 8511 EGRET LAKES LN
 CONT: P & T CONSTRUCTION CO.
 TEL: (561)833-0614
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FOR ALL ROOFING MATERIALS.
  
 4)PROVIDE A DETAIL WALL SECTION OF THE BAR AREA
 INCLUDING THE EQUIPMENT LOCATION.
  
 5)THE EMBEDMENT FOR THE 3/16" TAPCONS SHOWS 1/2". IS
 THIS CORRECT OR IS IT AND ERROR? PLEASE CLARIFY. SEE
 SHEET (T1)
  
 6)R802.1.6.1TRUSS DESIGN DRAWINGS, PREPARED IN
 COMFORMANCE WIITH THIS SECTION SHALL BE PROVIDED TO THE
 BUILDING OFFICIAL PRIOR TO INSTALLATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  