| Plan Review Notes For Permit 07010935 |
| Permit Number |
07010935 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-18 11:27:23 | DENIED BY BUILDING | | | | | | 1)INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES AND | | | ITS CORRESPONDING DESIGN PRESSURE WILL BE INSTALLED. | | | CIRCLE THE APPROPRIATE ONE ON PAGE 26 OF THE NOA. | | | | | | 2) THE FASTENER SPACING LISTED FOR THE FIELD ON THE | | | HVHZ FORM DOES NOT MATCH ANY OF THE FASTENING OPTIONS | | | ON PAGE 26 OF THE PRODUCT APPROVAL. | | | | | | 3) USING THE FASTENER SPACING FOR THE BASE SHEET | | | ATTACHMENT FOR RING SHANK NAILS AND TIN CAPS WITH | | | MAXIMUM DESIGN PRESSURE OF -45 PSF IN THE RAS 117 | | | CALCULATIONS, THE SPACING FOR THE CORNERS WILL BE 5" ON | | | CENTER AT THE LAP AND TWO ROWS AT 5" OC.PROVIDE RAS | | | 117 CALCULATIONS AS REQUIRED BY LIMITATION # 7 ON PAGE | | | 32 OF THE PRODUCT APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|