| 2007-07-19 11:01:51 | BUILDING PLAN REVIEW |
| | PERMIT: 07010901 |
| | ADD: 223 CLEMATIS ST |
| | CONT: MYRICK ENTERPRISES |
| | TEL: (954)445-2451 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 3RD REQUEST,FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE |
| | IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 4) 3RD REQUEST, 4) THE PERMIT APPLICATION, DESSCRIPTION |
| | OF WORK, INDICATES ONLY A INTERIOR DEMOLITION PERMIT |
| | WHERE AS PLANS INDICATE ADDITIONAL SCOPE OF WORK. |
| | PLEASE CORRECT THE PERMIT APPLICATION TO INCLUDE THE |
| | LARGER SCOPE OF WORK.106.1.2*OR IF A TRUE INTERIOR DEMO |
| | INDICATE SUCH ON PLAN. |
| | |
| | 5) COMPLIED. |
| | |
| | 6A) COMPLIED. |
| | |
| | 6B) COMPLIED. |
| | |
| | 6C) COMPLIED. |
| | |
| | 6D)ERROR, THE BUILDING TYPEOF CONSTRUCTION, AS |
| | DEFINED IN CHAPTER 3. THIS BUILDING IS A TYPE II-A TO |
| | BE SPRINKLERED. THIS IS A 4 STORY BUILDING,WITH THE 1 |
| | STORY INCREASE FROM A FULLY SPRINKLED BUILDING! |
| | THE OWNERS ARE TAKING THE AREA INCREASES GIVEN TO THEM |
| | BY THE SPINKLERS. |
| | THIS MEANS THIS SPACE WILL REQUIRE FIRE SPRINKLERS AND |
| | FIRE SPRINKLER PLANS. |
| | |
| | 6ECOMPLIED. |
| | |
| | 6F) YES A FIRE SPRINKLER WILL BE REQUIRED. |
| | |
| | 6G-H) COMPLIED. |
| | |
| | 7)COMPLIED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |