| 2007-02-06 15:42:13 | *****DENIED***** |
| | |
| | |
| | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE. |
| | |
| | 5.INDICATE THE LOCATION OF FIRE EXTINGUISHERS, EXIT |
| | LIGHTS, EMERGENCY LIGHTS, FIRE SPRINKLERS, FIRE ALARM |
| | DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE |
| | OF WORK? |
| | |
| | 6.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND IN OTHER AREAS? |
| | |
| | 7.WHAT IS THE OCCUPANT LOAD FOR THIS STRUCTURE AS |
| | DETERMINED PER THE OCCUPANT LOAD FACTORS OF NFPA 101, |
| | TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE |
| | SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE |
| | POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER |
| | IS GREATER. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED ON THE PLAN. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |