Plan Review Notes For Permit 07010901
Permit Number 07010901
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-06 15:42:13*****DENIED*****
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE.
  
 5.INDICATE THE LOCATION OF FIRE EXTINGUISHERS, EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE SPRINKLERS, FIRE ALARM
 DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE
 OF WORK?
  
 6.WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN OTHER AREAS?
  
 7.WHAT IS THE OCCUPANT LOAD FOR THIS STRUCTURE AS
 DETERMINED PER THE OCCUPANT LOAD FACTORS OF NFPA 101,
 TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE
 SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW