| 2007-01-21 13:26:12 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK |
| | BEING DICTATED ON PLANS IS EXTREMELY LOW FOR SCOPE OF |
| | WORK SHOWN. |
| | PLEASE SEE FBC ADMIN SECTION 108.3 |
| | PLEASE KNOW IF ONE IS NOT ADJUSTED FOR SCOPE AS SHOWN |
| | ON PLANS, ONE WILL BE ASSESSED USING THE FBC AND |
| | METHODS ADOPTED INTO THE 2004 FBC AND THE FBC |
| | ADMINISTRATIVE SECTIONS TO THE FBC. |
| | |
| | 2) NOTE: PLEASE SEE THE CODES RELEVANT FOR SCOPE OF |
| | WORK SHALL BE STATED ON PLANS. |
| | 2006 REVISIONS TO THE 2004 FBC, 2003 NFPA-101, 2002 |
| | NFPA-72 AND THE 2005 NFPA-70. |
| | PLEASE SEE PLANS SHALL STATE THE OCCUPANCY, LOAD ETC, |
| | WHICH WILL BE IN BUILDING REVIEW NOTES. |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHALL BE SIGNED, DATED AND |
| | SEALED BY THE ARCHITECT OF RECORD AS LISTED ON PLANS. |
| | FAC 61G1-16, FS 481.221 |
| | FBC ADMIN SECTION 106.1 |
| | |
| | 4) NOTE: PLEASE INDICATE NEW OR EXISTING REMAIN |
| | EMERGENCY LIGHT FIXTURES AND EXIT LIGHTING AS REQUIRED |
| | PER NFPA-101 7.8 AND 7.9. |
| | PLEASE ALSO SEE 700.12E AS CIRCUITING SHALL MEET THIS |
| | SECTION, IF IT DOES NOT ALREADY. |
| | **PLEASE BE SURE TO SEE POSSIBLE FIRE REVIEW COMMENTS. |
| | |
| | 5) NOTE: PLEASE SEE PLANS MENTIONS REPLACING CEILING |
| | GRID, PLEASE PROVIDE LIGHTING LAYOUT FOR EXISTING OR |
| | NEW FIXTURES FOR LOCATIONS. THIS CAN BE DONE AS |
| | REFLECTED CEILING PLANS IF ALL EXISTING. IF ANY OF |
| | THESE FIXTURES ARE GOING TO BE NEW, THEN PLEASE PROVIDE |
| | ON ELECTRICAL SHEETS ALONG WITH NOTE #4 ABOVE. |
| | |
| | |
| | ** PLEASE KNOW AS THE COMPLETE SCOPE OF WORK IS NOT |
| | EXACTLY CLEAR AT THIS TIME, THERE MAY BE COMMENTS ON |
| | THE NEXT REVIEW DEPENDING ON THE PLANS AND INFORMATION |
| | PROVIDED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |