| Plan Review Notes For Permit 07010880 |
| Permit Number |
07010880 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-27 13:11:25 | | | | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | SAME COMMENT AS LAST REVIEW. THERE IS AN ELECTRICAL | | | "PANEL" SHOWN ON THE ELECTRICAL SCHEMATIC. THIS WOULD | | | APPEAR TO BE A "POOL PANEL". IF IT IS EXISTING PLEASE | | | INDICATE ON THE PLAN. IF IT IS BEING INSTALLED AS PART | | | OF THIS PERMIT, SUBMIT THE FOLLOWING DETAILS ON THE | | | PLAN: | | | | | | MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE | | | SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL | | | RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|