2007-03-27 13:11:25 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 SAME COMMENT AS LAST REVIEW. THERE IS AN ELECTRICAL
 "PANEL" SHOWN ON THE ELECTRICAL SCHEMATIC. THIS WOULD
 APPEAR TO BE A "POOL PANEL". IF IT IS EXISTING PLEASE
 INDICATE ON THE PLAN. IF IT IS BEING INSTALLED AS PART
 OF THIS PERMIT, SUBMIT THE FOLLOWING DETAILS ON THE
 PLAN:
  
 MAKE THE FOLLOWING CORRECTIONS FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  