Plan Review Notes
Plan Review Notes For Permit 07010880
Permit Number 07010880
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-05 16:26:16DENIED
 REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101, SWIMMING
 POOLS;CITY OF WEST PALM BEACH AMENDMENTS TO FBC-2004
 CHAPTER 1, ADMINISTRATION
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1)SHEET 3 OF 3 PLEASE DELETE THE 2001 YEAR REFERENCE
 AND ADD 2004 YEAR REFERENCE IN ITS PLACE, PER FBC 2004
 CHAPTER 1, SECTION 106.1.1 INFORMATION ON ONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2)FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPER- ATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE MANUFACTURER CUT SHEET OR INDICATE
 THE MAKE AND MODEL NUMBER ON THE RESUBMITTED PRINTS.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  