2008-07-18 15:57:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION (ROOF CURB DETAIL).
  
 *** DENIED ***
  
 1) PER 2004 FBC 1509.7 THE 24"X24" FRESH AIR DUCT WILL
 NEED TO HAVE A MINIMUM OF 18 INCHES OF CLEARANCE ABOVE
 THE ROOF SURFACE. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;