Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 9
Notes
Date Text
2008-04-04 14:22:03** DENIED REVISIONS FOR THE 6TH REVIEW **
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS FIVE REVIEWS
 WHICH *STILL* REMAIN THE SAME. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE CALCULATIONS NOW SUBMITTED ARE METHOD *C* WHEN ALL
 PREVIOUS SUBMITTED CALCULATIONS WERE *A*.
 PLEASE SEE THE NEW *C* CALCULATIONS DO NOT CORRELATE
 WITH PLANS. PLEASE SEE NOT ALL INTERIOR FIXTURES ON
 PLANS FOR WATTAGE AS SHOWN AND COUNT CORRELATES WITH
 FIXTURE LEGEND AND SOME LIGHTING ON PLANS IS NOT ON THE
 INPUT DATA REPORT AT ALL.
 FOR EXAMPLE:
 SEE SHEET A-6.1 SHOWS LIGHTING NOT SHOWN ON ELECTRICAL
 PLANS FOR BATHROOMS. SEE THE ELECTRICAL PLANS FOR THESE
 SAME LOCATIONS AS FIXTURE LEGEND DOES NOT INCLUDE
 THESE. SEE THE FIXTURES ON A SHEETS AND E-SHEETS ARE
 SHOWN AS TWO COMPLETELY DIFFERENT FIXTURES.
 THESE ARE SHOWN AS COMPACT FLUORESCENT ON THE IDR.IN
 FACT ALL FIXTURES ARE SHOWN AS COMPACT FLUORESCENT.
 SEE TRACK LIGHTING WHICH IS ON PLANS IS STILL NOT
 INCLUDED.
 ** THERE IS SOME SORT OF NOTE WHICH WAS CUT IN HALF BY
 PRINTING WHICH NOTES THESE AS EXISTING HOWEVER THIS IS
 NOT THE CASE.
 PLEASE SEE THE *A* FIXTURES ANDVERIFY THESE ARE SHOWN
 AS DUAL 26W TROFFERS. SEE LITHONIA LIGHTING AS THESE
 ARE NOT LISTED W/ COMPANY. THESE ARE SHOWN ON THE IDR
 AS COMPACT FLUORESCENT ALSO.
 PLEASE SEE THE FIXTURES ON PLANS FOR 2-PERSON BOOTH
 LOCATIONS ARE NOT ON FIXTURE LEGEND NOR ARE THEY ON
 CALCULATIONS.
  
 2) NOTE: THIS REVIEWER HAS CALLED AND SPOKEN TO
 ENGINEER?S OFFICE SEVERAL TIMES AND YET PLANS AND
 CALCULATIONS ARE STILL NOT BEING CORRECTED.A MEETING
 WITH THE OWNER AND CONTRACTOR BEING PRESENT IS BEING
 REQUESTED BEFORE NEW PLANS OR CALCULATIONS ARE
 SUBMITTED.
 PLANS ARE ONCE AGAIN BEING RETAINED AND MAY BE
 SUBMITTED TO THE FLORIDA BOARD OF ENGINEERS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]