| 2008-04-04 14:22:03 | ** DENIED REVISIONS FOR THE 6TH REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS FIVE REVIEWS |
| | WHICH *STILL* REMAIN THE SAME. PLEASE SEE 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | THE CALCULATIONS NOW SUBMITTED ARE METHOD *C* WHEN ALL |
| | PREVIOUS SUBMITTED CALCULATIONS WERE *A*. |
| | PLEASE SEE THE NEW *C* CALCULATIONS DO NOT CORRELATE |
| | WITH PLANS. PLEASE SEE NOT ALL INTERIOR FIXTURES ON |
| | PLANS FOR WATTAGE AS SHOWN AND COUNT CORRELATES WITH |
| | FIXTURE LEGEND AND SOME LIGHTING ON PLANS IS NOT ON THE |
| | INPUT DATA REPORT AT ALL. |
| | FOR EXAMPLE: |
| | SEE SHEET A-6.1 SHOWS LIGHTING NOT SHOWN ON ELECTRICAL |
| | PLANS FOR BATHROOMS. SEE THE ELECTRICAL PLANS FOR THESE |
| | SAME LOCATIONS AS FIXTURE LEGEND DOES NOT INCLUDE |
| | THESE. SEE THE FIXTURES ON A SHEETS AND E-SHEETS ARE |
| | SHOWN AS TWO COMPLETELY DIFFERENT FIXTURES. |
| | THESE ARE SHOWN AS COMPACT FLUORESCENT ON THE IDR.IN |
| | FACT ALL FIXTURES ARE SHOWN AS COMPACT FLUORESCENT. |
| | SEE TRACK LIGHTING WHICH IS ON PLANS IS STILL NOT |
| | INCLUDED. |
| | ** THERE IS SOME SORT OF NOTE WHICH WAS CUT IN HALF BY |
| | PRINTING WHICH NOTES THESE AS EXISTING HOWEVER THIS IS |
| | NOT THE CASE. |
| | PLEASE SEE THE *A* FIXTURES ANDVERIFY THESE ARE SHOWN |
| | AS DUAL 26W TROFFERS. SEE LITHONIA LIGHTING AS THESE |
| | ARE NOT LISTED W/ COMPANY. THESE ARE SHOWN ON THE IDR |
| | AS COMPACT FLUORESCENT ALSO. |
| | PLEASE SEE THE FIXTURES ON PLANS FOR 2-PERSON BOOTH |
| | LOCATIONS ARE NOT ON FIXTURE LEGEND NOR ARE THEY ON |
| | CALCULATIONS. |
| | |
| | 2) NOTE: THIS REVIEWER HAS CALLED AND SPOKEN TO |
| | ENGINEER?S OFFICE SEVERAL TIMES AND YET PLANS AND |
| | CALCULATIONS ARE STILL NOT BEING CORRECTED.A MEETING |
| | WITH THE OWNER AND CONTRACTOR BEING PRESENT IS BEING |
| | REQUESTED BEFORE NEW PLANS OR CALCULATIONS ARE |
| | SUBMITTED. |
| | PLANS ARE ONCE AGAIN BEING RETAINED AND MAY BE |
| | SUBMITTED TO THE FLORIDA BOARD OF ENGINEERS. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |