| 2008-03-21 11:44:12 | ** DENIEDREVISIONS FOR THE FIFTH REVIEW ** |
| | |
| | *** PLEASE SEE THE SAME COMMENTS AS PREVIOUSLY |
| | MENTIONED STILL ARE IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:PLEASE SEE FBC 13-400.3.A, 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2, .1.3 AS ALL LIGHTING ON PLANS |
| | NEEDS TO CORRELATE WITH THE INPUT DATA REPORT AND |
| | ENERGY CALCULATIONS. |
| | PLEASE SEE FIXTURES ON PLANS SUCH AS EXTERIOR LIGHTS |
| | ARE NEW ON-SITE AND ARE NOT EXISTING AS SHOWN ON PLANS. |
| | IN EITHER CASE IF USING METHOD *A*, ALL KNOWN IS |
| | REQUIRED. HOW CAN THE EXTERIOR FIXTURES SHOWN ON THE |
| | IDR BE 12W FIXTURES? THE WATTAGE FOR ALL LIGHTS IS |
| | BASED ON FIXTURE WATTAGE, NOT BULBS. THE EXTERIOR |
| | FIXTURES ARE NOT 12W FIXTURES. |
| | PLEASE SEE THE INTERIOR LIGHTS ALSO DO NOT MATCH. THERE |
| | ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN THE |
| | IDR. |
| | PLEASE COMPLETE THE FIXTURES LEGEND FOR ALL FIXTURES AS |
| | THIS LOCATION HAS ALL NEW INSTALLED.THIS SHOULD |
| | INCLUDE TRACK FIXTURES, OUTSIDE ETC. |
| | ** CALCULATIONS ARE REQUIRED TO BE SIGNED BY THE |
| | PREPARER AND ALSO SIGNED BY THE OWNER AGENT. PLEASE DO |
| | NOT TYPE/PRINT THE PREPARERS NAME AND HAVE THE OWNER |
| | AGENT SPACE SIGNED BY PREPARER. |
| | FBC 13-103.1.1.1 |
| | |
| | 2) NOTE: PLEASE SEE NEW SHEETS E-2 ARE MISSING TITLE |
| | BLOCKS FOR FIRM. |
| | FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE THE BUILDING COMPONENTS ON PLANS |
| | SHALL ALSO MATCH THE PLANS FOR COMPLIANCE IN METHOD *A* |
| | CALCULATIONS. |
| | PLEASE KNOW ITEMS SUCH AS INSULATION ETC DO NOT MATCH |
| | THE IDR. THIS WILL PART OF THE BUILDING REVIEW |
| | COMMENTS. |
| | |
| | 4) NOTE: THIS REVIEW CALLED ENGINEERING OFFICE AND |
| | ENGINEER OF RECORD AND WENT OVER COMMENTS ONCE AGAIN. |
| | |
| | 5) NOTE: PLEASE SEE THE PAGES BEING REVISED ARE $10 PER |
| | PAGE AND CALCULATIONS COUNT AS ONE PAGE ALSO. |
| | FEE WILL BE DUE WHEN RESUBMITTING NEW PLANS. |
| | |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |