Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 8
Notes
Date Text
2008-03-21 11:44:12** DENIEDREVISIONS FOR THE FIFTH REVIEW **
  
 *** PLEASE SEE THE SAME COMMENTS AS PREVIOUSLY
 MENTIONED STILL ARE IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE FBC 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2, .1.3 AS ALL LIGHTING ON PLANS
 NEEDS TO CORRELATE WITH THE INPUT DATA REPORT AND
 ENERGY CALCULATIONS.
 PLEASE SEE FIXTURES ON PLANS SUCH AS EXTERIOR LIGHTS
 ARE NEW ON-SITE AND ARE NOT EXISTING AS SHOWN ON PLANS.
 IN EITHER CASE IF USING METHOD *A*, ALL KNOWN IS
 REQUIRED. HOW CAN THE EXTERIOR FIXTURES SHOWN ON THE
 IDR BE 12W FIXTURES? THE WATTAGE FOR ALL LIGHTS IS
 BASED ON FIXTURE WATTAGE, NOT BULBS. THE EXTERIOR
 FIXTURES ARE NOT 12W FIXTURES.
 PLEASE SEE THE INTERIOR LIGHTS ALSO DO NOT MATCH. THERE
 ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN THE
 IDR.
 PLEASE COMPLETE THE FIXTURES LEGEND FOR ALL FIXTURES AS
 THIS LOCATION HAS ALL NEW INSTALLED.THIS SHOULD
 INCLUDE TRACK FIXTURES, OUTSIDE ETC.
 ** CALCULATIONS ARE REQUIRED TO BE SIGNED BY THE
 PREPARER AND ALSO SIGNED BY THE OWNER AGENT. PLEASE DO
 NOT TYPE/PRINT THE PREPARERS NAME AND HAVE THE OWNER
 AGENT SPACE SIGNED BY PREPARER.
 FBC 13-103.1.1.1
  
 2) NOTE: PLEASE SEE NEW SHEETS E-2 ARE MISSING TITLE
 BLOCKS FOR FIRM.
 FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE THE BUILDING COMPONENTS ON PLANS
 SHALL ALSO MATCH THE PLANS FOR COMPLIANCE IN METHOD *A*
 CALCULATIONS.
 PLEASE KNOW ITEMS SUCH AS INSULATION ETC DO NOT MATCH
 THE IDR. THIS WILL PART OF THE BUILDING REVIEW
 COMMENTS.
  
 4) NOTE: THIS REVIEW CALLED ENGINEERING OFFICE AND
 ENGINEER OF RECORD AND WENT OVER COMMENTS ONCE AGAIN.
  
 5) NOTE: PLEASE SEE THE PAGES BEING REVISED ARE $10 PER
 PAGE AND CALCULATIONS COUNT AS ONE PAGE ALSO.
 FEE WILL BE DUE WHEN RESUBMITTING NEW PLANS.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]