| 2008-03-14 12:33:16 | ** DENIEDREVIEW ** |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE FROMTHREE |
| | PREVIOUS REVIEWS WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. PLEASE SEE THE LIGHTING WHICH IS SHOWN ON THE |
| | PLANS DOES NOT MATCH WITH THE LIGHTING SHOWN ON THE |
| | INPUT DATA REPORTS OR ENERGY CALCULATIONS. |
| | FOR EXAMPLE; THE IDR DOES NOT SHOW ANY OUTSIDE LIGHTS. |
| | HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW |
| | OUTSIDE LIGHTS. |
| | PLEASE SEE THE IDR SHOWS METAL BLDG, HOWEVER THE PLANS |
| | DOES NOT SHOW A METAL BUILDING. ETC. |
| | PLEASE SEE COMMENTS FROM BUILD REVIEWER AS ALL |
| | INSULATION COMPONENTS, ROOFING ETC NEEDS TO CORRELATE. |
| | THE INSULATION RATINGS ETC. |
| | 13-415.2, 13-400.3.A. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |