| 2008-03-04 14:50:04 | ** DENIEDREVIEW ** |
| | |
| | ** PLEASE SEE MANY COMMENTS FROM THE PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:PLEASE SEE VALUE WAS STILL NOT INCREASED FOR |
| | THE INCREASED SCOPE OF WORK. PLEASE SUBMIT COMPLETE |
| | CONTRACTS FOR SCOPE OF WORK WITH CORPORATE OR A VALUE |
| | WILL BE ASSESSED. |
| | FBC 108.3 |
| | PLEASE SEE ATTACHED NOTES FROM PREVIOUS REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS OF |
| | METHOD *A* ARE BEING SUBMITTED. THESE ARE INCOMPLETE AS |
| | NO INPUT DATA REPORT WAS SUBMITTED. |
| | PLEASE ALSO KNOW THAT USING METHOD *A* REQUIRES |
| | BUILDING COMPLIANCE FOR ALL COMPONENTS INCLUDING A/C. |
| | HOWEVER THESE ARE STILL NOT COMPLETE AND NOT ALL |
| | COMPONENTS ON PLANS ARE SHOWN TO VERIFY. |
| | PLEASE SEE THAT LIGHTING PERFORMANCE CALCULATIONS STILL |
| | NEED TO MEET 13-415.2, 13-415.2.ABC.1.1 AND |
| | 13-415.2.ABC.1.3. |
| | 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-415.1.A, |
| | 13-415.1.B, 13-415.1.C ETC |
| | |
| | 3) NOTE: PLEASE SEE THE NEW ELECTRICAL SHEETS SUBMITTED |
| | ARE NOT SEALED WITH RAISED SEAL AS REQUIRED PER FS |
| | 471.025 AND FAC 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL WITH |
| | RESPECT TO ENERGY CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE SEE NOTES STATED ON PREVIOUS REVIEW. |
| | PLEASE REMOVED ALL OLD/VOIDED SHEETS AND BE SURE SETS |
| | ONLY CONTAIN NEW SHEETS IN COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | AS STATED ON PREVIOUS REVIEW PLEASE DO NOT ATTACH |
| | SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. |
| | |
| | 6) NOTE: PLEASE KNOW AS MANY ITEMS ARE BEING REPEATED, |
| | ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | |
| | *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR |
| | REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |