Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 5
Notes
Date Text
2008-01-30 17:26:34** DENIED REVIEW **
  
 *** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING AND SEVERAL NEW COMMENTS
 BASED ON SUBSTANTIAL AMOUNT OF CHANGES NOW MADE WHICH
 WERE NOT ON PREVIOUS PLANS SUBMITTED.
  
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK AT SITE IS TO BE REVISED.
 THE REVISED VALUE HAS BEEN INCREASED TO $119,000
 HOWEVER SCOPE OF WORK AT SITE HAS NOW INCREASED ONCE
 AGAIN ON PLANS WHICH EXCEED PREVIOUS PLANS SCOPE OF
 WORK.
 PLEASE SUBMIT SIGNED CONTRACTS FOR WORK DONE AT
 LOCATION.
 PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC.
  
 2) NOTE:PLEASE SEE PREVIOUS NOTE #2. PLEASE SEE A
 METHOD *A* IS STILL BEING SUBMITTED. PLEASE SEE
 13-101.1.3
 PLEASE SEE THE INPUT DATA REPORT AS REQUIRED TO BE PART
 OF THE ENERGY CALCULATIONS IS STILL NOT BEING
 SUBMITTED. THE REVIEW AND SIGN OFF FROM OTHER REVIEW
 TRADE(S) HAS BEEN VOIDED.
 THIS WOULD REQUIRE THE ENTIRE STRUCTURE TO BE BROUGHT
 INTO COMPLIANCE. PLEASE SUBMIT COMPLETED ENERGY
 CALCULATIONS AS NO INPUT DATA REPORT WAS SUBMITTED
 WHICH IS REQUIRED TO BE PART OF THE ENERGY
 CALCULATIONS.
 13-415.1.A, 13-415.2, 13-415.1.B,13-415.1.ABC.1.3 ETC
  
 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE
 NOTES ON PLANS.
  
 4) NOTE: PLEASE BE SURE TO REMOVE OLD/VOIDED SHEETS
 FROM SETS. PLEASE ALSO DO NOT ATTACH SUPPORTING
 DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL RISER HAS NOW BEEN
 COMPLETELY REVISED.
 PLEASE SUBMIT COMPLETED INFORMATION FOR THE FOLLOWING:
 PLEASE SUBMIT AIC RATINGS PER 110.9
 PLEASE SEE 250.6, 250.24 AS NO *EQUIPMENT GROUNDING
 CONDUCTORS* ARE PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE THE RISER SHOWS NEW 400AMP MAIN PANEL YET NO
 INFORMATION IS SHOWN. IN FACT THE RISER SHOWS NEW
 200AMP DISCONNECT AND NEW 200AMP MCB.???
 PLEASE SEE NO CHANGE WAS MADE FROM PREVIOUS METER CAN.
 THE OLD METER CAN WAS LESS IN AMPERAGE.
 PLEASE SEE THE RISER ALSO SHOWS NEW EQUIPMENT GROUNDING
 CONDUCTORS TO FPL WHICH ARE NOT PERMITTED.
 PLEASE SEE PLANS DO NOT SHOW LOCATIONS OF THE NEW
 SERVICE EQUIPMENT.
 PLEASE SEE THE MAINS CAN NOT BE CONFIRMED TO BE
 GROUPED.
 PLEASE SEE NO NEW LOCATION FOR COMPLETE GROUNDING
 ELECTRODE SYSTEM AS SERVICE HAS NOW BEEN INCREASED AND
 CHANGED.
 AT THIS TIME THERE ARE TOO MANY CODE SECTIONS TO BE
 GIVEN.
 PLEASE SEE 230.70, 230.71, 230.72, 110.26, 240.4,
 250.50, ETC ONLY A FEW ARE NOTED, PLEASE SEE 2005
 NFPA-70
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2004 FBC W/2006 REVISIONS.
 ** THIS IS REQUIRED ON ELECTRICAL PLANS.
  
 7) NOTE: PLEASE COMPLETE ELECTRICAL PLANS FOR ALL
 LIGHTING ETC FOR INSIDE AS WELL AS OUTSIDE. THE
 EXTERIOR LIGHTING AS SHOWN ON ARCHITECTURAL SHEETS AS
 WELL AS LIGHTING LOCATED ON-SITE IS NOT BEING SHOWN.
 PLEASE COMPLETE.
 NEC 2005
 FBC 106.5.1.2, 106.1.2
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  