| Date |
Text |
| 2008-01-30 17:26:34 | ** DENIED REVIEW ** |
| | |
| | *** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING AND SEVERAL NEW COMMENTS |
| | BASED ON SUBSTANTIAL AMOUNT OF CHANGES NOW MADE WHICH |
| | WERE NOT ON PREVIOUS PLANS SUBMITTED. |
| | |
| | ** DENIED REVISION ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK AT SITE IS TO BE REVISED. |
| | THE REVISED VALUE HAS BEEN INCREASED TO $119,000 |
| | HOWEVER SCOPE OF WORK AT SITE HAS NOW INCREASED ONCE |
| | AGAIN ON PLANS WHICH EXCEED PREVIOUS PLANS SCOPE OF |
| | WORK. |
| | PLEASE SUBMIT SIGNED CONTRACTS FOR WORK DONE AT |
| | LOCATION. |
| | PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL |
| | LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC. |
| | |
| | 2) NOTE:PLEASE SEE PREVIOUS NOTE #2. PLEASE SEE A |
| | METHOD *A* IS STILL BEING SUBMITTED. PLEASE SEE |
| | 13-101.1.3 |
| | PLEASE SEE THE INPUT DATA REPORT AS REQUIRED TO BE PART |
| | OF THE ENERGY CALCULATIONS IS STILL NOT BEING |
| | SUBMITTED. THE REVIEW AND SIGN OFF FROM OTHER REVIEW |
| | TRADE(S) HAS BEEN VOIDED. |
| | THIS WOULD REQUIRE THE ENTIRE STRUCTURE TO BE BROUGHT |
| | INTO COMPLIANCE. PLEASE SUBMIT COMPLETED ENERGY |
| | CALCULATIONS AS NO INPUT DATA REPORT WAS SUBMITTED |
| | WHICH IS REQUIRED TO BE PART OF THE ENERGY |
| | CALCULATIONS. |
| | 13-415.1.A, 13-415.2, 13-415.1.B,13-415.1.ABC.1.3 ETC |
| | |
| | 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE |
| | NOTES ON PLANS. |
| | |
| | 4) NOTE: PLEASE BE SURE TO REMOVE OLD/VOIDED SHEETS |
| | FROM SETS. PLEASE ALSO DO NOT ATTACH SUPPORTING |
| | DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. |
| | |
| | 5) NOTE: PLEASE SEE THE ELECTRICAL RISER HAS NOW BEEN |
| | COMPLETELY REVISED. |
| | PLEASE SUBMIT COMPLETED INFORMATION FOR THE FOLLOWING: |
| | PLEASE SUBMIT AIC RATINGS PER 110.9 |
| | PLEASE SEE 250.6, 250.24 AS NO *EQUIPMENT GROUNDING |
| | CONDUCTORS* ARE PERMITTED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE SEE THE RISER SHOWS NEW 400AMP MAIN PANEL YET NO |
| | INFORMATION IS SHOWN. IN FACT THE RISER SHOWS NEW |
| | 200AMP DISCONNECT AND NEW 200AMP MCB.??? |
| | PLEASE SEE NO CHANGE WAS MADE FROM PREVIOUS METER CAN. |
| | THE OLD METER CAN WAS LESS IN AMPERAGE. |
| | PLEASE SEE THE RISER ALSO SHOWS NEW EQUIPMENT GROUNDING |
| | CONDUCTORS TO FPL WHICH ARE NOT PERMITTED. |
| | PLEASE SEE PLANS DO NOT SHOW LOCATIONS OF THE NEW |
| | SERVICE EQUIPMENT. |
| | PLEASE SEE THE MAINS CAN NOT BE CONFIRMED TO BE |
| | GROUPED. |
| | PLEASE SEE NO NEW LOCATION FOR COMPLETE GROUNDING |
| | ELECTRODE SYSTEM AS SERVICE HAS NOW BEEN INCREASED AND |
| | CHANGED. |
| | AT THIS TIME THERE ARE TOO MANY CODE SECTIONS TO BE |
| | GIVEN. |
| | PLEASE SEE 230.70, 230.71, 230.72, 110.26, 240.4, |
| | 250.50, ETC ONLY A FEW ARE NOTED, PLEASE SEE 2005 |
| | NFPA-70 |
| | |
| | 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2004 FBC W/2006 REVISIONS. |
| | ** THIS IS REQUIRED ON ELECTRICAL PLANS. |
| | |
| | 7) NOTE: PLEASE COMPLETE ELECTRICAL PLANS FOR ALL |
| | LIGHTING ETC FOR INSIDE AS WELL AS OUTSIDE. THE |
| | EXTERIOR LIGHTING AS SHOWN ON ARCHITECTURAL SHEETS AS |
| | WELL AS LIGHTING LOCATED ON-SITE IS NOT BEING SHOWN. |
| | PLEASE COMPLETE. |
| | NEC 2005 |
| | FBC 106.5.1.2, 106.1.2 |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |