Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 4
Notes
Date Text
2007-12-03 14:50:13 
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK AT SITE IS TO BE REVISED.
 THE WORK AT SITE HAS GONE WAY BEYOND THE OLD APPLIED
 VALUE OF $40K.
 PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC.
  
 2) NOTE: PLEASE SEE A METHOD *A* IS BEING SUBMITTED FOR
 WHOLE BUILDING COMPLIANCE. THIS WOULD REQUIRE THE
 ENTIRE STRUCTURE TO BE BROUGHT INTO COMPLIANCE. PLEASE
 SUBMIT COMPLETED ENERGY CALCULATIONS AS NO INPUT DATA
 REPORT WAS SUBMITTED WHICH IS REQUIRED TO BE PART OF
 THE ENERGY CALCULATIONS.
 13-415.1.A, 13-415.2, 13-415.1.ABC.1.3 ETC
  
 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE
 NOTES ON PLANS.
  
 4) NOTE: PLEASE PROVIDE DOCUMENTATION FOR NEW DESIGNERS
 OF RECORD.
 FAC 61G15, FS 471.025
  
 5) NOTE: PLEASE SEE SOME SHEETS ARE MISSING TITLE
 BLOCKS PER FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT
 GROUNDING CONDUCTORS* ARE NOT INSTALLED BEFORE THE
 FIRST MEANS OF DISCONNECT.
  
 7) NOTE: PLEASE PROVIDE COMPLETED ELECTRICAL PLANS FOR
 THE ENTIRE SCOPE OF ELECTRICAL WORK ONSITE-.
 THE NEW REVISED ELECTRICAL PLANS DO NOT REFLECT WORK AT
 SITE WHICH HAS BEEN VIEWED BY THIS REVIEWER.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  