| 2007-12-03 14:50:13 | |
| | ** DENIED REVISION ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK AT SITE IS TO BE REVISED. |
| | THE WORK AT SITE HAS GONE WAY BEYOND THE OLD APPLIED |
| | VALUE OF $40K. |
| | PLEASE SEE FBC 108.3 AS THE VALUE IS TO INCLUDE ALL |
| | LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC. |
| | |
| | 2) NOTE: PLEASE SEE A METHOD *A* IS BEING SUBMITTED FOR |
| | WHOLE BUILDING COMPLIANCE. THIS WOULD REQUIRE THE |
| | ENTIRE STRUCTURE TO BE BROUGHT INTO COMPLIANCE. PLEASE |
| | SUBMIT COMPLETED ENERGY CALCULATIONS AS NO INPUT DATA |
| | REPORT WAS SUBMITTED WHICH IS REQUIRED TO BE PART OF |
| | THE ENERGY CALCULATIONS. |
| | 13-415.1.A, 13-415.2, 13-415.1.ABC.1.3 ETC |
| | |
| | 3) NOTE: PLEASE SEE 13-413.1.ABC.1.1, .1.2 AND PROVIDE |
| | NOTES ON PLANS. |
| | |
| | 4) NOTE: PLEASE PROVIDE DOCUMENTATION FOR NEW DESIGNERS |
| | OF RECORD. |
| | FAC 61G15, FS 471.025 |
| | |
| | 5) NOTE: PLEASE SEE SOME SHEETS ARE MISSING TITLE |
| | BLOCKS PER FAC 61G15-23.002 |
| | |
| | 6) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT |
| | GROUNDING CONDUCTORS* ARE NOT INSTALLED BEFORE THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 7) NOTE: PLEASE PROVIDE COMPLETED ELECTRICAL PLANS FOR |
| | THE ENTIRE SCOPE OF ELECTRICAL WORK ONSITE-. |
| | THE NEW REVISED ELECTRICAL PLANS DO NOT REFLECT WORK AT |
| | SITE WHICH HAS BEEN VIEWED BY THIS REVIEWER. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |