2007-12-03 14:12:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) SEE PLAN PAGE M-2. THE 3" WATER HEATER VENT PIPE MAY
 NOT BE WITHIN 10 FT. OF THE OUTDOOR AIR INTAKE, SEE
 2004 FBC/M 401.5.1
  
 2) SEE PLAN PAGE M-2 DUCT SUPPORT ON ROOF DETAIL, STATE
 TYPE AND SIZE OF ANCHORS TO SECURE THE DUCT SUPPORT TO
 THE ROOF.
  