| 2007-07-04 10:29:52 | 2007-07-04 10:29:52 |
| | |
| | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ONE OF THE COMMENTS MADE AND NOTED |
| | AS **IMPORTANT** ON PREVIOUS REVIEW WAS NOT DONE. |
| | PLEASE SEE THE NOTE REQUESTED FOR ALL OLD/VOIDED SHEETS |
| | TO BE *REMOVED* FROM SETS. IT ALSO REQUESTED FOR ONLY |
| | THE NEW SHEETS TO BE INSERTED INTO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. PLEASE SEE NOTE WHICH THEN |
| | REQUESTED FOR ONLY ONE SET/COPY OF THE *OLD/VOIDED* |
| | SHEETS TO BE SUBMITTED FOR REFERENCE ONLY. |
| | PLEASE SEE ALL OF THE OLD/VOIDED SHEETS WERE LEFT IN |
| | SETS. PLEASE REMOVE. |
| | |
| | |
| | 2) NOTE:PLEASE SEE PREVIOUS NOTE MENTIONED FOR MORE |
| | INFORMATION ON FIXTURES AND TO COMPLETE FIXTURE LEGEND. |
| | THIS NEEDED TO CORRELATE WITH PLANS FOR ALL FIXTURES AS |
| | SHOWN ON ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE |
| | THE FIXTURE LEGEND IS NOT COMPLETE AS NO INFORMATION |
| | WAS PROVIDED. |
| | |
| | ** PREVIOUS NOTES #3 AND #4** |
| | ** PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL |
| | *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON |
| | ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES, |
| | PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND |
| | WITH OTHER FIXTURES. |
| | FBC 106.1.2 ADMIN SECTON. |
| | |
| | ** PLEASE SEE PLANS MENTIONS THAT THE EXISTING CIRCUITS |
| | WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES ON THE |
| | WATTAGES OF THE EXISTING FIXTURES BEING REMOVED AND THE |
| | UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING |
| | INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE |
| | NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS |
| | WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES. |
| | 106.1.2, 106.5.3.1.2. |
| | NEC 240.4, 310.16, 410, 110.3 ETC. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE #5 BELOW REQUESTED |
| | THE INSTALLATION OF WINDOW RECEPTACLES DIRECTLY ABOVE |
| | WINDOWS. THE RESPONSE LETTER MENTIONS TO SEE SHEET |
| | E-1.0, HOWEVER NONE ARE LOCATED ON PLANS AS MENTIONED. |
| | THE SAME NOTE APPLIES. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE VERIFY IF THERE ARE NEW OR EXISTING WINDOW |
| | RECEPTACLES PER 210.62/220.12 |
| | FBC 106.1.2 |
| | |
| | 4) NOTE:PLEASE SEE PREVIOUS NOTE #7 AS IT REQUESTED |
| | LIGHTING CLARIFICATION FOR THE EXISTING BATH ROOMS AS |
| | THEY INDICATED EM TYPE LIGHT FIXTURES, HOWEVER SEE THE |
| | PLANS NOW DO NOT SHOWOR INDICATE ANY LIGHTING IN THE |
| | BATHROOMS AND ONLY SHOWS *J* FOR JUNCTION BOX. THIS IS |
| | NOT ACCEPTABLE TO THE LIFE SAFETY CODE, THIS OFFICE OR |
| | THE FIRE MARSHAL OFFICE. |
| | PLEASE INDICATE SOME SORT OF LIGHT FIXTURES IN THE |
| | BATHROOMS WHICH WILL BE REQUIRED. |
| | |
| | ** PREVIOUS NOTE #7** |
| | PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT LIGHTS |
| | PER NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED |
| | TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER |
| | EMERGENCY CONDITIONS. |
| | IF EXISTING, PLEASE SHOW. |
| | PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE |
| | *EM* FIXTURES, ARE THESE BATTERY BACK UP? |
| | |
| | 5) NOTE: PLEASE BE SURE TO CORRELATE ALL ELECTRICAL ON |
| | ARCHITECTURAL SHEETS WITH THAT AS SHOWN ON THE |
| | ELECTRICAL SHEETS. |
| | PLEASE SEE THESE ARE DIFFERENT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-04 10:02:42 | 2007-07-04 10:02:42 |
| | PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS COMPLETED. |