Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-04 10:29:522007-07-04 10:29:52
  
 ** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ONE OF THE COMMENTS MADE AND NOTED
 AS **IMPORTANT** ON PREVIOUS REVIEW WAS NOT DONE.
 PLEASE SEE THE NOTE REQUESTED FOR ALL OLD/VOIDED SHEETS
 TO BE *REMOVED* FROM SETS. IT ALSO REQUESTED FOR ONLY
 THE NEW SHEETS TO BE INSERTED INTO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE NOTE WHICH THEN
 REQUESTED FOR ONLY ONE SET/COPY OF THE *OLD/VOIDED*
 SHEETS TO BE SUBMITTED FOR REFERENCE ONLY.
 PLEASE SEE ALL OF THE OLD/VOIDED SHEETS WERE LEFT IN
 SETS. PLEASE REMOVE.
  
  
 2) NOTE:PLEASE SEE PREVIOUS NOTE MENTIONED FOR MORE
 INFORMATION ON FIXTURES AND TO COMPLETE FIXTURE LEGEND.
 THIS NEEDED TO CORRELATE WITH PLANS FOR ALL FIXTURES AS
 SHOWN ON ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE
 THE FIXTURE LEGEND IS NOT COMPLETE AS NO INFORMATION
 WAS PROVIDED.
  
 ** PREVIOUS NOTES #3 AND #4**
 ** PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL
 *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON
 ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES,
 PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND
 WITH OTHER FIXTURES.
 FBC 106.1.2 ADMIN SECTON.
  
 ** PLEASE SEE PLANS MENTIONS THAT THE EXISTING CIRCUITS
 WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES ON THE
 WATTAGES OF THE EXISTING FIXTURES BEING REMOVED AND THE
 UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING
 INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE
 NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS
 WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES.
 106.1.2, 106.5.3.1.2.
 NEC 240.4, 310.16, 410, 110.3 ETC.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #5 BELOW REQUESTED
 THE INSTALLATION OF WINDOW RECEPTACLES DIRECTLY ABOVE
 WINDOWS. THE RESPONSE LETTER MENTIONS TO SEE SHEET
 E-1.0, HOWEVER NONE ARE LOCATED ON PLANS AS MENTIONED.
 THE SAME NOTE APPLIES.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE VERIFY IF THERE ARE NEW OR EXISTING WINDOW
 RECEPTACLES PER 210.62/220.12
 FBC 106.1.2
  
 4) NOTE:PLEASE SEE PREVIOUS NOTE #7 AS IT REQUESTED
 LIGHTING CLARIFICATION FOR THE EXISTING BATH ROOMS AS
 THEY INDICATED EM TYPE LIGHT FIXTURES, HOWEVER SEE THE
 PLANS NOW DO NOT SHOWOR INDICATE ANY LIGHTING IN THE
 BATHROOMS AND ONLY SHOWS *J* FOR JUNCTION BOX. THIS IS
 NOT ACCEPTABLE TO THE LIFE SAFETY CODE, THIS OFFICE OR
 THE FIRE MARSHAL OFFICE.
 PLEASE INDICATE SOME SORT OF LIGHT FIXTURES IN THE
 BATHROOMS WHICH WILL BE REQUIRED.
  
 ** PREVIOUS NOTE #7**
 PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT LIGHTS
 PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED
 TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER
 EMERGENCY CONDITIONS.
 IF EXISTING, PLEASE SHOW.
 PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE
 *EM* FIXTURES, ARE THESE BATTERY BACK UP?
  
 5) NOTE: PLEASE BE SURE TO CORRELATE ALL ELECTRICAL ON
 ARCHITECTURAL SHEETS WITH THAT AS SHOWN ON THE
 ELECTRICAL SHEETS.
 PLEASE SEE THESE ARE DIFFERENT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-04 10:02:422007-07-04 10:02:42
 PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.