2007-08-24 14:21:31BUILDING PLAN REVIEW
 PERMIT:07010866
 ADD:3231S. DIXIE HIGHWAY
 CONT:WAYJOHN INC.
 TEL: (561)683-8444
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 2 NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 RESPONCE TO CORRECTIONS SUBMITTED
  
  
 (1) WHEN RE-SUBMITTING PLANS FOR CORRECTIONS MADE,
 PLEASE PROCESSASFOLLOWS:
  (A)INDICATE THE CORRECTIONS BY CLOUDING THE
 CORRECTED AREAS
  (B)REMOVE THE OLD SHEET AND INSERT THE NEW CORRECTED
 SHEET INTO THE PLAN.
  (C) SUBMIT THE OLD SHEETS SEPARATE FROM THE CORRECTED
 PLAN FOR THE PLAN REVIEWER?S REFERENCE
  
 (2) F.S.713.13 (2)THE NOTICE OF COMMENCEMENT
 RECORDED ON 12/21/06EFFECTIVE FOR 90 DAYS FROM
 RECORDING
 HAS EXPIRED.PLEASE RESUBMIT A NEW RECORDED NOC
  
 (3) FBC EXISTING:304.1SHEETT. 1.0PLAN
 SPECIFIES LEVELTHIS IS A LEVEL2 ALTERATION
  
 (4) FBC1604.5SHEETA.3.0CHANGEWIND IMPORTANCE
 FACTOR TO CATEGORY II,FACTORI
  
 (8) FBC1503.4SHEETA-2.0HOW WILL STORM OR RAIN
 WATER BE REMOVED FROM AREA BELOW CANOPY IN
  THE ABSENCE OF PROTECTION?FURNISHROOF DRAIN AND
 2ND DRAIN OR OVERFLOW SCUPPER FOR DRAINAGE.
  
 (9) 9-B -72SHEET A- 4.0STUD PLATE CONNECTION
 SPECIFYUSPTIE DOWN FOR UP-LIFT RESTRAINT
  FBC 1703PROVIDE STATE OF FLORIDA PRODUCT APPROVALS
 FOR ALL STRUCTURAL CONNECTIONS.
  REQUIRES PRODUCT APPROVAL
  FLORIDA APPROVAL RATING
 PRODUCT APPROVAL FOR BACK-UP
  HAVE DESIGNER REVIEW AND ACKNOWLEDGE WITH SHOP STAMPS
 THEIR ACCEPTANCE.
  
 (10) SHEET A-4.1SPECIFIES PARAPET WALL SHEATHING ??
 SHEET A-4.0STATES 5/8?FURNISH CORRECT INFORMATION
  
 (11) PLEASE PLACE THEADA -1 SHEET BEHIND SHEET A-6.0.
 THIS WILL HELP THE CONTRACTOR AND FIELD INSPECTOR
 READILYIDENTIFY THE REQUIRED MEASUREMENTS FOR
 PLACEMENT OF BATHROOM ACCESSORIES.
  
  
  
  
  
  
  
  
  
  
  
  
  