| 2007-08-24 14:21:31 | BUILDING PLAN REVIEW |
| | PERMIT:07010866 |
| | ADD:3231S. DIXIE HIGHWAY |
| | CONT:WAYJOHN INC. |
| | TEL: (561)683-8444 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | 2 NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | |
| | RESPONCE TO CORRECTIONS SUBMITTED |
| | |
| | |
| | (1) WHEN RE-SUBMITTING PLANS FOR CORRECTIONS MADE, |
| | PLEASE PROCESSASFOLLOWS: |
| | (A)INDICATE THE CORRECTIONS BY CLOUDING THE |
| | CORRECTED AREAS |
| | (B)REMOVE THE OLD SHEET AND INSERT THE NEW CORRECTED |
| | SHEET INTO THE PLAN. |
| | (C) SUBMIT THE OLD SHEETS SEPARATE FROM THE CORRECTED |
| | PLAN FOR THE PLAN REVIEWER?S REFERENCE |
| | |
| | (2) F.S.713.13 (2)THE NOTICE OF COMMENCEMENT |
| | RECORDED ON 12/21/06EFFECTIVE FOR 90 DAYS FROM |
| | RECORDING |
| | HAS EXPIRED.PLEASE RESUBMIT A NEW RECORDED NOC |
| | |
| | (3) FBC EXISTING:304.1SHEETT. 1.0PLAN |
| | SPECIFIES LEVELTHIS IS A LEVEL2 ALTERATION |
| | |
| | (4) FBC1604.5SHEETA.3.0CHANGEWIND IMPORTANCE |
| | FACTOR TO CATEGORY II,FACTORI |
| | |
| | (8) FBC1503.4SHEETA-2.0HOW WILL STORM OR RAIN |
| | WATER BE REMOVED FROM AREA BELOW CANOPY IN |
| | THE ABSENCE OF PROTECTION?FURNISHROOF DRAIN AND |
| | 2ND DRAIN OR OVERFLOW SCUPPER FOR DRAINAGE. |
| | |
| | (9) 9-B -72SHEET A- 4.0STUD PLATE CONNECTION |
| | SPECIFYUSPTIE DOWN FOR UP-LIFT RESTRAINT |
| | FBC 1703PROVIDE STATE OF FLORIDA PRODUCT APPROVALS |
| | FOR ALL STRUCTURAL CONNECTIONS. |
| | REQUIRES PRODUCT APPROVAL |
| | FLORIDA APPROVAL RATING |
| | PRODUCT APPROVAL FOR BACK-UP |
| | HAVE DESIGNER REVIEW AND ACKNOWLEDGE WITH SHOP STAMPS |
| | THEIR ACCEPTANCE. |
| | |
| | (10) SHEET A-4.1SPECIFIES PARAPET WALL SHEATHING ?? |
| | SHEET A-4.0STATES 5/8?FURNISH CORRECT INFORMATION |
| | |
| | (11) PLEASE PLACE THEADA -1 SHEET BEHIND SHEET A-6.0. |
| | THIS WILL HELP THE CONTRACTOR AND FIELD INSPECTOR |
| | READILYIDENTIFY THE REQUIRED MEASUREMENTS FOR |
| | PLACEMENT OF BATHROOM ACCESSORIES. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |