| 2007-02-28 18:24:16 | *****DENIED***** |
| | |
| | |
| | 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE |
| | SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.THE BUILDING OR PORTIONS OF THE BUILDING WILL BE |
| | PERMITTED TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY |
| | WHERE THE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE |
| | PROTECTION ARE IN PLACE AND MAINTAINED. |
| | |
| | 6.ON THE APPROPIATE PLAN SHEETS, FURTHER SPECIFY |
| | NORTH, SOUTH , EAST, AND WEST EXTERIOR ELEVATIONS FOR |
| | THIS STRUCTURE. |
| | |
| | 7.ON SHEET A-3.0, POST THE NUMERICAL ADDRESS ON THE |
| | FRONT SIDE (EAST) ELEVATION.AS PER WEST PALM BEACH |
| | CODE , THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT |
| | AND NO LESS THAN 1"IN WIDTH. |
| | |
| | 8.PLEASE SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY |
| | LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE STRUCTURE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |