Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-04 18:25:04 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN
 SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF
 FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND
 THE 2005 NFPA-70.
 PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A
 MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER
 TRADES.
 2004 FBC W/2006 REVISONS)
 2005 NFPA-70 NEC.
 2002 NFPA-72 (IF APPLICABLE)
 2003 NFPA-101 LIFE SAFETY CODE.
  
 2) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT
 APPEARS TO BE *INITIALS* FROM THE DESIGN PROFESSIONAL.
 IF THIS IS INDEED THE LEGAL SIGNATURE OF THE SAID
 DESIGNER OF RECORD, PLEASE SUBMIT A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR LEGAL SIGNATURE
 VERIFICATION.
 FAC 61G15-23.002, AND FS 471.025
 PLEASE BE SURE THE NOTARY FOLLOWS THE GUIDELINES AS SET
 FORTH IN FS 117.05 FOR CORRECT STATEMENT ON LETTER.
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL
 *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON
 ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES,
 PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND
 WITH OTHER FIXTURES.
 FBC 106.1.2 ADMIN SECTON.
  
 4) NOTE: PLEASE SEE PLANS MENTIONS THAT THE EXISTING
 CIRCUITS WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES
 ON THE WATTAGES OF THE EXISTING FIXTURES BEING REMOVED
 AND THE UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING
 INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE
 NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS
 WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES.
 106.1.2, 106.5.3.1.2.
 NEC 240.4, 310.16, 410, 110.3 ETC.
  
 5) NOTE: PLEASE VERIFY IF THERE ARE NEW OR EXISTING
 WINDOW RECEPTACLES PER 210.62/220.12
 FBC 106.1.2
  
 6) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER
 600.5.
 FBC 106.1.2
  
 7) NOTE: PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT
 LIGHTS PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED
 TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER
 EMERGENCY CONDITIONS.
 IF EXISTING, PLEASE SHOW.
 PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE
 *EM* FIXTURES, ARE THESE BATTERY BACK UP?
  
 ** PLEASE BE AWARE OF ANY POSSIBLE COMMENTS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]