| 2007-02-04 18:25:04 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE CODES ADOPTED AND IN DESIGN |
| | SHALL BE STATED ON THE PLANS. |
| | PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE STATE OF |
| | FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004 FBC AND |
| | THE 2005 NFPA-70. |
| | PLEASE BE SURE TO STATE THE FOLLOWING ON THE PLANS AT A |
| | MINIMUM AND ANY OTHERS WHICH MAY BE MENTIONED BY OTHER |
| | TRADES. |
| | 2004 FBC W/2006 REVISONS) |
| | 2005 NFPA-70 NEC. |
| | 2002 NFPA-72 (IF APPLICABLE) |
| | 2003 NFPA-101 LIFE SAFETY CODE. |
| | |
| | 2) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT |
| | APPEARS TO BE *INITIALS* FROM THE DESIGN PROFESSIONAL. |
| | IF THIS IS INDEED THE LEGAL SIGNATURE OF THE SAID |
| | DESIGNER OF RECORD, PLEASE SUBMIT A SIGNED, DATED, |
| | SEALED AND NOTARIZED LETTER FOR LEGAL SIGNATURE |
| | VERIFICATION. |
| | FAC 61G15-23.002, AND FS 471.025 |
| | PLEASE BE SURE THE NOTARY FOLLOWS THE GUIDELINES AS SET |
| | FORTH IN FS 117.05 FOR CORRECT STATEMENT ON LETTER. |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PLANS INDICATE SEVERAL |
| | *J-BOXES* FOR WHAT IS SHOWN AS LIGHT FIXTURES ON |
| | ARCHITECTURAL SHEETS. PLEASE SHOW LIGHT FIXTURES, |
| | PLEASE LABEL AND PROVIDE INFORMATION ON FIXTURE LEGEND |
| | WITH OTHER FIXTURES. |
| | FBC 106.1.2 ADMIN SECTON. |
| | |
| | 4) NOTE: PLEASE SEE PLANS MENTIONS THAT THE EXISTING |
| | CIRCUITS WILL BE UTILIZED FOR NEW LIGHTS, HOWEVER BASES |
| | ON THE WATTAGES OF THE EXISTING FIXTURES BEING REMOVED |
| | AND THE UNKNOWN OF THE NEW FIXTURES AND LIGHTING BEING |
| | INSTALLED, PLEASE PROVIDE THIS INFORMATION ON THE |
| | NUMBER OF EXISTING CIRCUITS WHICH WILL BE USED. THIS |
| | WILL BE CONFIRMED WITH THE FIXTURES AND WATTAGES. |
| | 106.1.2, 106.5.3.1.2. |
| | NEC 240.4, 310.16, 410, 110.3 ETC. |
| | |
| | 5) NOTE: PLEASE VERIFY IF THERE ARE NEW OR EXISTING |
| | WINDOW RECEPTACLES PER 210.62/220.12 |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER |
| | 600.5. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SHOW NEW OR EXISTING EMERGENCY AND EXIT |
| | LIGHTS PER NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE THAT MINIMUM LEVELS OF LIGHTING ARE REQUIRED |
| | TO THE PUBLIC RIGHT OF WAY OUT OF BUILDING UNDER |
| | EMERGENCY CONDITIONS. |
| | IF EXISTING, PLEASE SHOW. |
| | PLEASE SEE THE NEW REMODELED BATHROOMS INDICATE TYPE |
| | *EM* FIXTURES, ARE THESE BATTERY BACK UP? |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE COMMENTS WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |