Plan Review Notes
Plan Review Notes For Permit 07010866
Permit Number 07010866
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-07 16:54:23BUILDING PLAN REVIEW
 PERMIT: 07010866
 ADD: 3231 S DIXIE HWY
 CONT: DARRELL SHAFRANSKI CONSTRUCTION
 TEL: (772)569-5862
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SHEET C-1.0 ACCESSIBLE PARKING:
 PLEASE PROVIDE SIGNAGE, 11-4.6.4 SIGNAGE.
 EACH ACCESSIBLE PARKING SPACE MUST BE PROMINENTLY
 OUTLINED WITH BLUE PAINT, AND MUST BE REPAINTED AS
 NECESSARY, TO BE CLEARLY DISTINGUISHABLE AS A PARKING
 SPACE DESIGNATED FOR PERSONS WHO HAVE DISABILITIES AND
 MUST BE POSTED WITH A PERMANENT ABOVE-GRADE SIGN
 BEARING THE INTERNATIONAL SYMBOL OF ACCESSIBILITY,
 MEETING THE REQUIREMENTS OF COLOR AND DESIGN APPROVED
 BY THE DEPARTMENT OF TRANSPORTATION, OF SECTION
 11-4.30.7 AND THE CAPTION ?PARKING BY DISABLED PERMIT
 ONLY.? SUCH SIGN ERECTED AFTER OCTOBER 1, 1996, MUST
 INDICATE THE PENALTY FOR ILLEGAL USE OF THE SPACE.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 WHAT LEVEL OF ALTERATION WILL THIS BE , 2004 EXISTING
 BUILDING CODE?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THEOCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS WALL SYSTEMS
 B) TRUSS ANCHORS
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) SHEET A-4.1 INDICATES THE FRAMING DETAIL FOR THE
 NEWLY DESIGNEDTOWER, SHEET A-4.1 INDICATES THE NEW
 TOWER HAS THE CENTER OPEN AND THE INSIDE WALLS HAVE A
 MODIFIED BITUMEN ROOFING MEMBRANE, THERE APPEARS TO BE
 NO ROOF DRAIN NOR OVERFLOW SCUPPERS TO ALLOW THE RAIN
 WATER OUT OF THIS BOX LOOKING TOWER. HOW WILL RAIN
 WATER
 BE DRAINED?
  
 SHEET A-3.0 INDICATES A STRIPED ILLUMINATED TOWER BY
 KFC/ VENDOR, IS THIS TO BE UNDER SEPERATE PERMIT? IS
 THIS TO KEEP OUT RAIN OR IS THIS ADVERTISEMENT
 PURPOSES?
 WILL THERE BE ENGINEERING SHOWING COMPLIANCE WITH 140
 MPH WIND LOADS?
  
 9) PLANS SHOW AWNINGS BUT NO INFORMATION HAS BEEN
 PROVIDED AS TO THE TYPE OF AWNING IF FIXED IN PLACE, IF
 CLOTH ETC, TO BE UNDER A SEPERATE PERMIT?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-03-07 16:32:34 


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved