| Permit Number |
07010842 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-21 15:25:54 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1, SHT T1 DEMOLITION REQUIREMENTS NOTE #3. IN THE | | | REMOVAL OF ANY PART OF THE DRAINAGE SYSTEM, DEAD ENDS | | | ARE PROHIBITED. SECTION 704.5. ALL CAPPED SANITARY | | | PIPING SHALL BE INDICATED ON THE PLANS AND SHALL NOT BE | | | COVERED PRIOR TO INSPECTION. | | | | | | 2. SHT P1 A SANITARY RISER ISOMETRIC DIAGRAM IS | | | REQUIRED SHOWING ALL CAPPED LINES AND ALL NEW LINES | | | INCLUDING VENTS. SHOW ALL PIPE SIZES, TRAPS, VENTS ETC. | | | SECTION 106.3.5.1.3(4)(6)(13). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|