Plan Review Notes
Plan Review Notes For Permit 07010842
Permit Number 07010842
Review Stop P
Sequence Number 1
Notes
Date Text
2007-02-21 15:25:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1, SHT T1 DEMOLITION REQUIREMENTS NOTE #3. IN THE
 REMOVAL OF ANY PART OF THE DRAINAGE SYSTEM, DEAD ENDS
 ARE PROHIBITED. SECTION 704.5. ALL CAPPED SANITARY
 PIPING SHALL BE INDICATED ON THE PLANS AND SHALL NOT BE
 COVERED PRIOR TO INSPECTION.
  
 2. SHT P1 A SANITARY RISER ISOMETRIC DIAGRAM IS
 REQUIRED SHOWING ALL CAPPED LINES AND ALL NEW LINES
 INCLUDING VENTS. SHOW ALL PIPE SIZES, TRAPS, VENTS ETC.
 SECTION 106.3.5.1.3(4)(6)(13).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]