| 2007-03-07 14:07:07 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING |
| | POOLS: |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1) ** NO**,FBC-2004 SEC. 424.2.6.6.5, OR FBCR-2004 |
| | SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPERATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. |
| | NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR |
| | INDICATE THE MAKE AND MODEL NUMBER ON THE RESUBMITTED |
| | PRINTS. PLEASE REFERENCE THE ATTACHED EXAMPLE OF VACUUM |
| | OR PRESSURE CLEANER FITTING WITH THE ABOVE |
| | INFORMATION. |
| | |
| | 2) **NO**,FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | NOTE: PLEASE REFERENCE THE ATTACHED EXAMPLE OF AN |
| | 1-1/2" ATMOSPHERIC VENT TABLE COMPLYING WITH 3 SECOND |
| | RELEASE. PLEASE SUBMIT A TABLE WITH 1" VENT COMPLYING |
| | WITH 3 SECOND RELEASE ON THE RESUBMITTAL. |
| | |
| | 3) OK |
| | |
| | **IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: |
| | WHEN RESUBMITTING, PLEASE REPLACE ONLY SHEETS WHICH |
| | HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |