2007-07-13 11:31:44DENIED 4TH TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1.NOTE: THE FIXTURE LAYOUT OF THE PROPOSED BATHROOM
 HAS CHANGED FROM THE PREVIOUS SUBMITTALS AS WELL AS THE
 SHOWER BEING CHANGED TO A TUB. THE RESUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM ON SHEET 1, STILL DOES NOT
 REFLECT THIS NEW FLOOR PLAN LAYOUT. THE ISOMETRIC SHALL
 REFLECT THE FLOOR PLAN PER 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND 106.3.5.4 (9) PLUMBING.
 PLEASE REFERENCE THE RED LINE CORRECTIONS OF THE
 SANITARY RISER ON SHEET 1 THAT REFLECTS THE FLOOR PLAN
 AND IS CODE COMPLIANT FOR THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]