Plan Review Notes
Plan Review Notes For Permit 07010788
Permit Number 07010788
Review Stop P
Sequence Number 3
Notes
Date Text
2007-04-06 09:32:20DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3.**NO**PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THE RESUBMITTED DRAWINGS ARE NOT AN ISOMETRIC.
 PLEASE REFERENCE THE ATTACHED SANITARY ISOMETRIC RISER
 DIAGRAM TO THE PLUMBING COMMENTS THAT REFLECTS THE
 FLOOR PLAN AND IS CODE COMPLIANT.
  
 4. **NO** PER FBC-2004 PLUMBING, SECTION 405.3.1
 FIXTURE CLEARENCES: THERE SHALL BE AT LEAST TWENTY ONE
 INCHES (21") CLEARENCE IN FRONT OF THE WATER CLOSET AND
 LAVATORY TO ANY WALL, FIXTURE OR DOOR.
 NOTE: THIS COMMENT STILL IS NOT ADDRESSED. THESE
 MEAUSUREMENTS INDICATING MINIMUM CLEARENCES MUST BE ON
 THE RESUBMITTED DRAWINGS TO PASS PLUMBING PLAN REVIEW.
  
 5. **OK**
  
 6. **NO**PER FBC-2004 PLUMBING, SECTION 417.4.1 WALL
 AREA: THE SHOWER WALLS MUST EXTEND TO A HEIGHT OF 6
 FEET ABOVE THE FLOOR LEVEL OF THE ROOM OR 70 INCHES
 ABOVE THE SHOWER FLOOR AND BE CONSTRUCTED OF SMOOTH,
 NONCORROSIVE AND NONABSORBENT MATERIALS TO PROTECT THE
 BUILDING MATERIALS FROM WATER DAMAGE.
 NOTE: THIS COMMENT IS STILL NOT BEING ADDRESSED. PLEASE
 ADDRESS THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  