2007-04-06 10:01:56*** DENIED ***
 1) AS NOTED IN LAST TWO REVIEWS 1-30-07 AND 3-8-07. THE
 PROPOSED BATHROOM WILL NEED A WINDOW OR A EXHAUST FAN,
 PLEASE SHOW ON PLANS.
 ** FROM LAST REVIEW. BATHROOMS, WATER CLOSET
 COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH AGGREGATE GLAZING AREA IN WINDOWS OF NOT LESS THAN
 3 SQUARE FEET, ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM
 ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50
 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR
 CONTINUOUS VENTILATION. VENTILATION AIR FROM THE SPACE
 SHALL BE EXHAUSTED DIRECTLY TO THE OUTSIDE. PLEASE SHOW
 ON PLANS A WINDOW OR A LIGHT AND FAN, PER 2004 FBC/R
 R303.3.
  
 2) AS NOTED IN LAST TWO REVIEW 1-30-07 AND 3-8-07. THE
 VALUE ON THE PERMIT APPLICATION IS TO LOW, THE VALUE
 MUST INCLUDE ALL LABOR AND MATERIALS AT A FAIR MARKET,
 REPLACEMENT COAST. PLEASE ADJUST THE VALUE OR THE
 BUILDING DEPARTMENT WILL NEED TO USING MARSHALL & SWIFT
 BUILDING COST, PER 2004 FBC WPB AMEND. 108.3.
  