Plan Review Notes
Plan Review Notes For Permit 07010788
Permit Number 07010788
Review Stop B
Sequence Number 3
Notes
Date Text
2007-04-06 16:41:43DENIED BY BUILDING ( 3RD REVIEW)
  
 1)FBC * 106.1.2 QUALITY OF PLANS
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 NOTE: THIS IS THE THIRD TIME PLANS HAVE BEEN SUBMITTED
 THAT WERE INSUFFICENT. PLANS ARE REQUIRED TO BE
 DRAFTSMAN QUALITY AND DRAWN TO SCALE WITH ALL
 DIMENSIONS SPECIFIED.
  
 2) THE 2004 FBC EXISTING BUILDING CODE SPECIFIES THIS
 WORK AS A LEVEL 2 ALTERATION. PLEASE SPECIFY "LEVEL 2
 ALTERATION" ON THE PLANS.
  
 3)THE PLANS ARE MISSING REQUIRED DIMENSIONS.
  
 4) VALUE OF WORK IS TOO LOW. THE VALUE HAS BEEN
 INCREASED TO $2500.00.
  
 5) ADDRESS COMMENTS FROM OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714